The two probe inputs can be interrelated with the two relay outputs for the thermometer, 
thermostat and the timing functions in cold and heat applications.

CONFIGURATION

 allows that some parameters are 

ADJUSTABLE

 or not by the 

USER

 so 

that he or she has the exclusive information and adjustment that the device’s use requires. 
The functions of the front part keys as well as the display of temperatures can be modified, 
while the configuration with a password can be blocked.

Warnings

The use of the unit different to the manufacturer’s instructions voids the safety qualification. 
To ensure correct operation of the apparatus, only NTC type probes supplied by AKO should 
be used. Between -40 ºC and +20 ºC, when the probe is extended up to 1.000m with 

2

minimum 0,5mm  cable, deviation will be less than 0.25 ºC (probe extension cable ref. 

AKO-15586

)

Versions and references

N

 

Installation

Fastening units for panel mounting

Fastening units for DIN rail mounting

Connection

Front panel functions

The controller must be installed in a place protected from vibrations, water and corrosive 
gases, and where the ambient temperature does not surpass the values specified in the 
technical data.
In order for the panel mounting units to be suitable having IP65 protection, the gasket 
should be installed properly between the apparatus and the perimeter of the panel cut-out 
where it is to be fitted. 
In order to give a correct reading, the probe has to be installed in a 
place without heat influences other than the temperature that is 
to be measured or controlled.

To  fix  the  unit,  place  the 
fasteners 1 over the sliders 2 
as shown in the figure. Move 
the fasteners in the direction 
of the arrow. By pressing tab 3 
the  fasteners  may  be  moved 
in  the  opposite  direction  of 
the arrow.

See diagram in the unit rating plate.
The probe and its lead shoud 

NEVER

 be installed in ducting along with power, control or 

power supply wiring. 
The power supply circuit should be connected with a minimum 2A, 230V, switch located 
close to the unit.

2

2

The cables should be of the type H05VV-F 2x0,5mm  or H05V-K 1x0,5mm . Section of 

2.

connecting wires for relays contacts must be between 1mm2 and 2,5mm

UP key:

 By pressing this key, the temperature in probe 2 is displayed.

By pressing it during 5 seconds, the R2 SET POINT is displayed.
In programming, it increases the value being displayed.
By default, the configuration of this key is factory-set for the preceding actions. However, it 
can be configured according to the options of parameters 42, 43.

Q

 DOWN key:

 By pressing this key during 5 seconds, the R1 SET POINT is displayed.

In programming, it decreases the value being displayed.
By default, the configuration of this key is factory-set for the preceding functions. However, 
it can be configured according to the options of parameters 44, 45.

UP + DOWN keys 

N

+

(panel mounting) or 

SET

 

key 

(DIN rail)

Pressing  these  keys  during  10  seconds  accesses  to  the  configuration  of  the  controller 
parameters.
Pressing these keys once accesses to the adjustment of the user’s parameters.
By  default,  the  configuration  of  these  keys  is  factory-set  for  the  preceding  function, 
however, they can be configured according to the options of parameter 46.

ºC: 

Permanent: Temperature display in ºC. Flashing, parameters programming phase.

ºF: 

Temperature display in ºF.

R1/R2:

 Relay R1/R2 activated.

It should only be programmed or modified by personnel who are fully conversant with the 
operation and possibilities of the equipment.

Press the CONFIGURE OR ADJUST keys for 10 seconds. The LED “ºC” will be flashing to 
indicate programming phase and the first parameter “01” will appear on the display.
Pressing the 

N

 key accesses the next parameter and the 

Q

 key will produce a return to the 

previous one.
Pressing DISPLAY VALUE key in the last display EP the controller will return to the current 
temperature display status and the LED “ºC” will stop flashing.

In order to display the current value of any parameter, select the desired parameter and 
press the DISPLAY VALUE keys. Once it is displayed, it can be modified by pressing the 

N

 or 

Q

 keys.

Pressing the ACCEPT THE NEW keys sets the new value. When this operation is performed, 
the programming returns to Level 1 (parameters).

ADJUSTMENT:

  Pressing  once  the  CONFIGURE  OR  ADJUST  keys  accesses  the  user’s 

parameters adjustment. The proceeding is the same as for the configuration and access is 
only possible to the parameters defined as adjustable by the user in the configuration. In 
order to access the parameters the parameter 39 parameter should be configured.

REMARK:

 If no key is pressed for 25 seconds in any of the previous steps, the controller will 

automatically return to the current temperature display status without modifying any of the 
parameters values. 

REMARK:

 When the time parameters are modified, the new values are applied once the 

current cycle is completed. In order for it to have an immediate effect, switch the controller 
off and then on again. 

LEDs

Configuration and adjustment

Level 1, Parameters

Level 2 Values

Configurable electronic thermostats with 2 relays and up to 2 probes

MODEL

AKO-14722

AKO-14723

AKO-15223

FASTENING UNIT

Panel mounting

Panel mounting

DIN raíl

POWER SUPPLY 50/60 Hz

_   

12 V ~

±

20%

230 V~ 

±

10%

230 V~ 

±

10%

PANEL CUT-OUT

28,5

70,5

3

2

1

max.

18 mm

61,5

44

90

35

58

45

LED ºC

LED R2

PRG

SET

UP

key

UP

key

Panel mounting

DIN Rail

DOWN

key

DOWN

key

key

SET

ºC

ºF

1
2
3
4

LED R1

LED ºC

LED

R1

ºC

ºF

LED

R2

LED ºF

1

2

3

4

LED ºF

EXIT

PROGRAMMING

CURRENT

TEMPERATURE

LEVEL 1

PARAMETERS

SIMULTANEOUSLY

SIMULTANEOUSLY

SIMULTANEOUSLY

LEVEL 2
VALUES

10 Sec.

DISPLAY

VALUE

CHANGE

VALUE

ACCEPT

THE NEW

CURRENT

VALUE

 

10 Sec.

CONFIGURE

OR ADJUST

ºC

ºF

SET

CURRENT

VALUE

1472H206 Ed.02