Configuration
Option only available if the advanced settings view is activated. Enables the management of
the server globally or individually.
Press on “Detect systems to update the server.
If the
system
management is selected, the available parameters are:
−
Name.
Shows the name of the system.
−
System ID.
Shows the number of the system within your installation.
−
Global Ventilation.
This menu allows you to activate/deactivate the fan mode
in all zones when the system is not actively heating or cooling any zones. By
default, the global ventilation is deactivated. When activated, the following
settings are used to configure Global Ventilation:
o
Every (min).
Configure the length of the interval (in minutes) between
periods of ventilation. Configurable from 5 to 40 minutes, in 5 minutes
increments (by default, 15 minutes).
o
Run For (min).
Configure the time duration that ventilation is activated
(in minutes). Configurable from 5 to 20 minutes, in 5 minutes increments
(by default, 10 minutes).
−
Auxiliary Heat.
This menu is used to enable/disable the auxiliary heat. By
default, the auxiliary heat is disabled. When auxiliary heat is enabled, the
following parameters are used to configure the operation of the auxiliary heat:
o
Available Stages.
Defines how many stages of auxiliary heat a system has.
o
First Supply Heat
. If the setting for Auxiliary heat is 1 or 2, then the first
system to supply heat must be defined as either: Heat Pump or Aux. Heat.
o
Fan Configuration.
Select between Electric (Fan on) or Furnace (Fan off)
option. If you select Electric option, define: