FWDB Low temperature floor ceiling-Technical Manual R32-50Hz
4 Water Drainage
4.1Gradient and Supporting
4.1.1 Keep the drainpipe sloping downwards at a gradient of at least 1/100. Keep the drainpipe as
short as possible and eliminate the air bubble.
4.1.2 The horizontal drainpipe should be short. When the pipe is too long, a prop stand must be
installed to keep the gradient of 1/100 and prevent bending. Refer to the following table for the specification
of the prop stand.
Diameter
Distance between the prop stands
Hard PVC pipe
25~40mm
1~1.5m
4.1.3. Precautions
①
The diameter of drainpipe should meet the drainage requirement at least.
②
The drainpipe should be heat-insulated to prevent atomization.
③
Drainpipe should be installed before installing indoor unit. After powering on, there is some water in
water-receiver plate. Please check if the drain pump can operate correctly.
④
All connection should be firm.
⑤
Wipe color on PVC pipe to note connection.
⑥
Climbing, horizontal and bending conditions are prohibited.
⑦
The dimension of drainpipe can’t less than the connecting dimension of indoor drainpipe.
⑧
Heat-insulation should be done well to prevent condensation.
⑨
Indoor units with different drainage type can’t share one convergent drainpipe.
4.2 Drainpipe Trap
4.2.1. If the pressure at the connection of the drainpipe is negative, it needs to design drainpipe
trap.
4.2.2. Every indoor unit needs one drainpipe trap.
4.2.3. A plug should be designed to do cleaning.
Plug
50
cm
50
cm
47
Summary of Contents for AW-FWDB018-N91
Page 15: ...FWDB Low temperature floor ceiling Technical Manual R32 50Hz 13 4 Service Space ...
Page 18: ...FWDB Low temperature floor ceiling Technical Manual R32 50Hz 16 6 2 AW FWDB024 N91 ...
Page 33: ...FWDB Low temperature floor ceiling Technical Manual R32 50Hz 4 2 AW YMDB024 H91 31 ...
Page 39: ...FWDB Low temperature floor ceiling Technical Manual R32 50Hz 8 2 AW YMDB024 H91 37 ...
Page 57: ...FWDB Low temperature floor ceiling Technical Manual R32 50Hz 55 ...