44
6.8
HydroSens™ InRoom
Before you start:
•
Confirm that electrical diagram is available.
•
Confirm that user manual is available.
Turn all fuses OFF.
•
Connect the cables for the sensors and ventilators to the HydroSens™, follow the electrical
diagram.
•
Connect power supply.
•
Check power supply voltage.
•
Check water supply is open and the water pressure.
•
Turn all fuses ON.
•
Wait for the display to start up.
•
to ensure that the system is stopped.
Airtec HydroSens
< InRoom %RH >
Software V. 2.04
System Stopped, F1=Start
Adjust by-pass:
•
> 2 sec. to goto ”Password” screen.
•
Enter password ”9963”, to accept, screen turns white.
Password
0000
Press OK
•
to goto ”Zone Overview” screen.
•
Check sensor signal.
•
to edit.
•
Set all setpoints to 0%.
•
Set Zone 1 setpoint above actual %RH.
•
to exit edit.
< Zone Overview >
%RH/set %RH/set
° 1 XXX/XXX ° 6 XXX/XXX
° 2 XXX/XXX 7 XXX/XXX
3 XXX/XXX ° 8 XXX/XXX
° 4 XXX/XXX 9 XXX/XXX
° 5 XXX/XXX °10 XXX/XXX
•
to goto ”System” screen.
•
Check the water pressure.
< System >
Operation, hours XXXXXX
Pump, hours XXXXXX
Oil, hours XXXXXX
Reset Service Yes
Pressure, Bar XX.X
Inverter, Amps XX.X
Show Service popup Yes
•
to goto ”Zone Control Setup” screen.
•
to edit.
•
Set Zone 1 to ”Sensor”.
•
to exit edit.
Zone Control Setup
Control Control
1 Sensor 6 Sensor
2 Ext+hyg 7 Ext+hyg
3 External 8 External
4 Off 9 Off
5 Off 10 Off
201218
F1 F2 F3
F1 F2 F3