To read the fault code do the following on the inverter
1. Press “Esc” 3 times, until the display shows “0,00 HERTZ”
2. Press
and a letter will start to blink
3. Press
until the letter is “b”, then press
4. Press
or
until “b007” is shown, then press
5. Read the Faut Code
6. Press “Esc” 3 times, until the display shows “0,00 HERTZ”
11.6
HydroSens™ inverter fault codes
No.
Fault
Description
Action
0
No Fault
No Fault present
-
2
Auxiliary Input.
External trip (Auxiliary) input.
•
Check remote wiring.
•
Verify communications programming for intentional fault.
3
Power Loss.
Single phase operation detected with excessive load.
•
Monitor the incoming AC line for low voltage or line power interruption.
•
Check input fuses.
•
Reduce load.
4
UnderVoltage.
DC bus voltage fell below the minimum value.
•
Monitor the incoming AC line for low voltage or line power interruption.
5
OverVoltage.
DC bus voltage exceeded maximum value.
•
Monitor the AC line for high line voltage or transient conditions. Bus overvoltage can also be
caused by motor regeneration. Extend the decel time or install dynamic brake option.
6
Motor Stalled.
Drive is unable to accelerate or decelerate motor.
•
Increase P041, A442, A444, A446 [Accel Time x] or reduce load so drive output current does not
exceed the current set by parameter A484, A485 [Current Limit x] for too long.
•
Check for overhauling load.
7
Motor Overload.
Internal electronic overload trip.
•
An excessive motor load exists.Reduce load so drive output current does not exceed the current
set by parameter P033 [Motor OL Current].
•
Verify A530 [Boost Select] setting.
8
Heatsink OvrTmp. Heatsink/Power Module temperature exceeds a predefined value.
•
Check for blocked or dirty heat sink fins. Verify that ambient temperature has not exceeded the
rated ambient temperature.
•
Check fan.
9
CC OvrTmp.
Control module temperature exceeds a predefined value.
•
Check product ambient temperature.
•
Check for airflow obstruction.
•
Check for dirt or debris.
•
Check fan.
12
HW OverCurrent.
The drive output current has exceeded the hardware current limit.
•
Check programming. Check for excess load, improper A530 [Boost Select] setting, DC brake
volts set too high or other causes of excess current.
13
Ground Fault.
A current path to earth ground has been detected at one or more of the drive
output terminals.
•
Check the motor and external wiring to the drive output terminals for a grounded condition.
21
Output Ph Loss.
Output Phase Loss (if enabled).
Configure with A557 [Out Phas Loss En].
•
Verify motor wiring.
•
Verify motor.
29
Analog In Loss.
An analog input is configured to fault on signal loss. A signal loss has
occurred.
Configure with t094 [Anlg In V Loss] or t097 [Anlg In mA Loss].
•
Check for broken/loose connections at inputs.
•
Check parameters.
33
Auto Rstrt Tries.
Drive unsuccessfully attempted to reset a fault and resume running for the
programmed number of A541 [Auto Rstrt Tries].
•
Correct the cause of the fault and manually clear.
38
Phase U to Gnd.
A phase to ground fault has been detected between the drive and motor in
this phase.
•
Check the wiring between the drive and motor.
•
Check motor for grounded phase.
•
Replace drive if fault cannot be cleared.
39
Phase V to Gnd.
40
Phase W to Gnd.
Alarm: External alarm
Fault
code: Cause
Solution
2001
External alarm signal is activated or Normally Open / Normally
Closed settings in HydroSens is setup wrong.
•
Check settings in HydroSens menu and compare with customer
request.
•
Check with customer to find external alarm source.
•
Alarm can only be reset after external equipment allow system to be
reset. Reset has to be done manually.