Airport Lighting Company
13
Advisory Circulars to determine the CCR step count requirement
.
To change the step count, navigate to:
Configuration Menu > CCR Config > Number of Steps > [1, 3, 5, 7]
The most common step counts are 3 and 5. Upon changing the step count, the CCR main screen
will reflect the accurate step-count nomenclature. 3 step CCRs identify the step counts as B10,
B30, and B100, while 5 step CCRs identify the step counts as B1, B2, B3, B4, and B5.
5.1.2 Calibrate Zeros
This command will have the CCR find a zero threshold in the input AC voltage. It is required when
making equipment changes to the CCR, or when a part is replaced.
Before completing this
calibration
: put the CCR in Local Mode and turn the output off.
Configuration Menu > CCR Config > Calibrate > Zeros > [Execute]