Therm-X MVHRU HR95
Technical Manual
Page 25 of 59
Version 2.4, 25/09/2020
7.
TECHNICAL DATA
7.1.
ELECTRICAL CHARACTERISTICS
Models without electric pre-heating coil and
…
without coil / with water heating coil / with WCO coil / with
DX coil
Unit
Type
Phase
Voltage
[V]
Frequency
[Hz]
Power Input
[kW]
Full load current
per phase [A]
HR95-080
1
230
50
0.40
2.8
HR95-150
1
230
50
1.00
6.5
HR95-250
1
230
50
1.00
6.5
HR95-350
3
400
50
1.85
3.7
HR95-450
3
400
50
1.85
3.7
HR95-550
3
400
50
3.60
5.5
Models without electric pre-heating coil and
…
with electric post heating coil
Unit
Type
Phase
Voltage
[V]
Frequency
[Hz]
Power Input
[kW]
Full load current
per phase [A]
HR95-080 V
1
230
50
1.80
8.8
HR95-150 V
1
230
50
3.70
18.0
HR95-250 V
3
400
50
5.80
13.5
HR95-350 V
3
400
50
8.30
13.0
HR95-450 V
3
400
50
10.00
15.0
HR95-550 V
3
400
50
14.50
21.0
HR95-080 H
1
230
50
1.80
8.8
HR95-150 H
1
230
50
3.70
18.0
HR95-250 H
3
400
50
5.80
13.5
HR95-350 H
3
400
50
8.30
13.0
Model with electric pre-heating coil and
…
without coil / with water heating coil / with WCO coil / with DX
coil
Unit
Type
Phase
Voltage
[V]
Frequency
[Hz]
Power Input
[kW]
Full load current
per phase [A]
HR95-080 V
1
230
50
3.10
14.5
HR95-150 V
3
400
50
6.30
13.3
HR95-250 V
3
400
50
9.40
18.6
HR95-350 V
3
400
50
13.55
20.6
HR95-450 V
3
400
50
16.85
25.4
HR95-550 V
3
400
50
21.90
32.0
HR95-080 H
1
230
50
3.10
14.5
HR95-150 H
3
400
50
6.30
13.3
HR95-250 H
3
400
50
9.40
18.6
HR95-350 H
3
400
50
13.60
20.6