Page 36
Electrical
ELECTROSTATIC DISCHARGE (ESD)
Precautions and Procedures
CAUTION
Electrostatic discharge can affect elec
tronic components. Take precautions
to neutralize electrostatic charge by
touching your hand and tools to metal
prior to handling the control.
The unit is equipped with a field makeup box. The makeup
box may be moved to the right side of the furnace to facili
tate
installation. Seal unused openings on left side with plugs
removed from right side. Secure the excess wire to the
existing harness to protect it from damage.
INTERIOR MAKE-UP BOX INSTALLATION
FIGURE 51
MAKE-UP
BOX
Left side
INTERIOR MAKE-UP BOX INSTALLATION
FIGURE 52
MAKE-UP
BOX
Right Side
remove and relocate
plug to unused
opening on left side
Refer to figure 55 for unit wiring.
The power supply wiring must meet Class I restric
tions. Protected by either a fuse or circuit breaker, se
lect circuit protection and wire size according to unit
nameplate.
NOTE -
Unit nameplate states maximum current draw.
Maximum over-current protection allowed is shown in table
12.
TABLE 12
95AF2DFV Model
Maximum Over-Current
Protection (Amps)
045V12B, 070V16B
15
090V20C, 110V20C
20
Holes
are on both sides of the furnace cabinet to facili
tate wiring.
Install a separate (properly sized) disconnect switch
near the furnace so that power can be turned off for
servicing.
Before
connecting the thermostat or the power wiring,
check to make sure the wires will be long enough for
servicing at a later date. Remove the blower access
panel to check the length of the wire.
Complete the wiring connections to the equipment.
Use the provided unit wiring diagram as shown in fig
ure 55. Use 18-gauge wire or larger that is suitable for
Class II rating for thermostat connections.
Electrically
ground the unit according to local codes or,
in the absence of local codes, according to the current
National Electric Code (ANSI/NFPA No. 70). A green
ground wire is provided in the field make-up box.
NOTE - The 95AF2DFV furnace contains electronic
components that are polarity sensitive. Make sure
that the furnace is wired correctly and is properly
grounded.
One line voltage “EAC” 1/4” spade terminal is provided
on the furnace integrated control. Any electronic air M
cleaner or other accessory rated up to one amp can be
connected to this terminal with the neutral leg of the cir
cuit being connected to one of the provided neutral ter
minals. See Figure 56 for control configuration. This
terminal is energized when the indoor blower is operat
ing.