RADOME A/C 

with Passport I/O 

 
 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 
 

Installation, Operation & Maintenance Manual

 

 

 
 
 
 
 
 
 
 
 
 
 
 
 

 
 
 
 
 

L-2283 

          Revised: 

9-29-04 

 

Summary of Contents for RADOME A/C

Page 1: ...RADOME A C with Passport I O Installation Operation Maintenance Manual L 2283 Revised 9 29 04...

Page 2: ...e display panel Face plate air sensor for accurate temperature control LED temperature displayed in Fahrenheit or Celsius Compressor pressure protection This manual is intended to provide the informat...

Page 3: ...ing servicing repairing or disposing of an appliance or industrial process refrigeration to knowingly vent or otherwise knowingly release or dispose of any Class I or Class II substance used as a refr...

Page 4: ...CZ 230VAC 50 60HZ 1Ph 11 E1010009 HSA16K C CZ CZ50 115 230VAC 50 60HZ 1Ph 12 E1010010 HSAS16K CZ CZ50 Split 230VAC 50 60HZ 1Ph 13 E1010013 HSAS16K Z Z50 Split W ELECTRIC HEAT 230VAC 50 60HZ 1Ph 14 E1...

Page 5: ...MENTS FOR IGNITION PROTECTION DO NOT INSTALL IN SPACES CONTAINING GASOLINE ENGINES TANKS LPG CPG CYLINDERS REGULATORS VALVES OR FUEL LINE FITTINGS FAILURE TO COMPLY MAY RESULT IN INJURY OR DEATH NOTIC...

Page 6: ...l connections shall be made with solderless terminals Turn off a c power supply circuit breaker before opening electric box Each a c unit installed requires its own dedicated circuit breaker OPERATION...

Page 7: ...le cooling FAN LED NOT USED ON RADOME A C HEAT LED NOT USED ON RADOME A C DISPLAY WINDOW Shows current temperature Also used in viewing and setting program parameters AIR SENSOR Dome temperature is de...

Page 8: ...h the system off press and hold the POWER button for five seconds until the letter P appears in the display window Release the button and the first parameter s setting appears followed by P 1 TO SELEC...

Page 9: ...nuous Pump P 13 Reverse Fan Speeds During Heating Mode rEF nor Normal Fan Operation rEF Reversed Fan In Heating P 14 Continuous Fan or Cycle Fan with Compressor con con Continuous Fan Operation CYC Cy...

Page 10: ...ut down delay P 7 Reserved for Future Option P 8 De Icing Cycle N A P 9 Reserved for Future Option P 10 Display Brightness Control The display brightness can be adjusted from four 4 to thirteen 13 Fou...

Page 11: ...condenser air flow Check for obstructions at condenser air inlet Fan is not running See below Coil is iced See below HPF is displayed on panel See below LPF is displayed on panel See below No air flow...

Page 12: ...date of manufacture Labor is not covered Environmental Air Systems Inc will repair or replace at its option components found to be defective due to faulty materials or workmanship when such component...

Page 13: ...275 Contact Gene Lawing Tel 206 660 2240 Fax 425 740 0246 E mail glawing earthlink net Delaware Maryland Pennsylvania Virginia New York New Jersey Connecticut Maine Massachusetts New Hamphsire Rhode I...

Page 14: ......

Page 15: ......

Page 16: ......

Page 17: ......

Page 18: ......

Page 19: ......

Page 20: ......

Page 21: ......

Page 22: ......

Page 23: ......

Page 24: ......

Page 25: ......

Page 26: ......

Page 27: ......

Page 28: ...drews Ave Ext Pompano Beach FL 33069 1497 USA Phone 954 973 2477 Facsimile 954 979 4414 Fleets Industrial Estate 26 Willis Way Poole Dorset BH15 3SU England Phone 44 0 870 3306101 Facsimile 44 0 870 3...

Reviews: