
50
If you are not sure how to measure superheat or sub-cooling
:
Superheat
•
Get an accurate suction line temperature on the suction line as close to the compressor inlet as possible. At
same time, attach a compound pressure gauge set to the system so as to read the low side suction pressure at
the suction service valve port (back seated valve stem to allow un-restricted refrigerant flow from evaporator
back to the compressor). Convert suction pressure to a saturated temperature as derived from a
pressure/temperature chart. Since the suction line temperature is the higher value, subtract the saturated
temperature from it to derive your superheat. If your wine cellar is already at specified conditions e.g., 57° F
(13°C), 55% RH), and if your superheat is very low, or zero, you may have overcharged your system
.
Sub-Cooling
•
With your compound pressure gauge set still installed with the high side connect to the valve port on the liquid
receiver (back seated valve stem to allow un-restricted refrigerant flow from condenser to evaporator). Convert
this liquid pressure to a saturated temperature from pressure/temperature chart. Next, obtain your liquid line
temperature by getting an accurate reading on the liquid line BEFORE the TXV expansion on the indoor side.
Obtain this temperature entering the evaporator unit. Subtract the liquid line temperature from the saturated
liquid temperature to derive the system sub-cooling
.
System Charging Amount:
Note: Each DS & WGS Model condensing unit is shipped with 16oz/.453kg of refrigerant charge
already, to be taken into account for below total amounts based on 25’/7.62 meters interconnect
length.
For system charge adjustments compared to 25’/7.62 meters factory baseline:
DS025, DS050, WGS40, WGS75 if
1/4”/.635cm OD (outside diameter) liquid line,
adjustments will be ~ .50oz/foot & .0465kg/meter
DS088, WGS100, DS200, WGS175 if
3/8”/.952cm OD (outside diameter) liquid line,
adjustments will be ~ 1.0oz/foot & .093kg/meter
For reference: Suggested total system charge based on factory testing using 25 feet (7.62 meters) of
interconnected piping in table below.
DS025
59-ounce total charge
WGS40
58-ounce total charge (1.64 kg)
DS050
55-ounce total charge
WGS75
64-ounce total charge (1.81 kg)
DS088
105-ounce total charge
WGS100
106-ounce total charge (3.01 kg)
DS200
108-ounce total charge
WGS175
110-ounce total charge (3.12 kg)
Summary of Contents for 99H0360-10
Page 12: ...12 Xtreme Low Ambient Illustrations Fig 1 Fig 2 Pressure cutout timer 33c0185 00...
Page 14: ...14 Condensing unit dimensions DS050 COND NO OPTIONS...
Page 15: ...15 Refrigeration Illustration of the system See next page for magnified image...
Page 16: ...16 Magnified Image of the Condensing Unit...
Page 17: ...17 Wiring Diagram for DS025 DS050 WGS40 WGS75...
Page 18: ...18 Wiring Diagram for DS088 and WGS100...
Page 19: ...19 Wiring Diagram for DS200 and WGS175 Units...
Page 20: ...20 Wiring Diagram for Replacement Fan Motor XR 115 230 Models...
Page 21: ...21 Wiring Diagram for DS025 and WGS40 Condensing Unit...
Page 22: ...22 Wiring Diagram for DS050 and WGS75 Condensing Unit...
Page 23: ...23 Wiring Diagram for DS088 and WGS100 Condensing Unit...
Page 24: ...24 Wiring Diagram for DS200 and WGS175 Condensing Unit...
Page 25: ...25 Ducted Split Systems Specifications 60Hz Models DS025 DS050 DS088 DS200...
Page 26: ...26 Ducted Split System Specifications 50 Hz Models WGS40 WGS75 WGS100 WGS175...
Page 44: ...44 Install refrigeration piping per local codes and ASHRAE guidelines...