Installation, Operation & Maintenance Parksafe Gas Detector
Rev: 9 10-20
10
OPERATION
First Power Up
1. 2. 3. 4.
1.
On connecting power, your gas detector Power LED will illuminate.
2.
The gas detector then enters a stabilisation phase for approximately 60 seconds – during this time the
Fault LED will flash indicating that the device is not yet ready for operation.
3.
The gas detector will then establish a Modbus data signal with the main control panel – during this
time the Fault LED will remain on.
4.
When a data signal is established with the main control panel, the Fault LED will switch off and the
detector will be in operation. Check your Parksafe panel for gas detector status.
Do not remove the gas sensor module under power!
LED Indicators
Power
The Power LED will remain illuminated when power to the detector is present.
Fault
An issue with the gas sensing module, i.e. it has been knocked or damaged.
The gas sensing module has reached the end of its expected lifecycle.
Alarm
The system is in alarm condition because dangerous gas levels have been detected.
Gas Alarm Levels
GAS TYPE
GOOD
PRE-ALARM
ALARM
Carbon Monoxide (CO)
> 25 ppm
25 -100 ppm
> 100 ppm
Nitrogen Dioxide (NO
2
)
< 0.7 ppm
0.7 - 2 ppm
> 2 ppm