© Agrowtek Inc. | www.agrowtek.com | Technology to Help You Grow™
13
Data registers are 16 bits wide with addresses using the standard MODICON protocol. Floating point values
use the standard IEEE 32-bit format occupying two contiguous 16 bit registers. ASCII values are stored with
two characters (bytes) per register in hexadecimal format. Coil registers are single bit values which control
and indicate the status of a relay; 1 = on, 0 = off.
Register Types
Supported Commands
MODBUS Holding Registers
Parameter
Description
Range
Type
Access
Address
Address
Device Slave Address
1 - 247
8 bit
R/W
40001
Serial#
Device Serial Number
ASCII
8 char
R
40004
DOM
Date of Manufacture
ASCII
8 char
R
40008
HW Version
Hardware Version
ASCII
8 char
R
40012
FW Version
Firmware Version
ASCII
8 char
R
40016
Timeout (seconds)
Turn off relays if no communication
0 - 32767
16 bit, unsigned
R/W
41001
Relay Closure Count
Relay 1
Unsigned Int
32 bit, unsigned
R
49001
Relay 2
49003
Relay 3
49005
Relay 4
49007
Relay 5
49009
Relay 6
49011
Relay 7
49013
Relay 8
49015
MODBUS Coil Registers
Parameter
Access
Address
Relay 1
R/W
1
Relay 2
R/W
2
Relay 3
R/W
3
Relay 4
R/W
4
Relay 5
R/W
5
Relay 6
R/W
6
Relay 7
R/W
7
Relay 8
R/W
8
0x01 Read Coils
0x03 Read Multiple Registers
0x05 Write Single Coil
0x06 Write Single Register
0x15 Write Multiple Coils
A request to use a function that is not available will return an illegal function error (0x01).
A request to read or write a register that is not available will return an illegal address error (0x02).
A request to read or write coils that are not available will return an illegal address error (0x02.)