TA Series of  Temperature Controller

         Instruction Manual

Thanks a lot for selecting   the  product!

Before operating this instrument, please carefully read this

manual and fully  understand its contents. If any probroms,

please  contact our sales or distributors whom you buy from.

This manual is subject  to change  without prior notice.

       

Applications

    TA series temperature controller is available for many TC & RTD

    input. It adopts some advanced techonology such as multi digital

    filter circuit, autotune  PID, fuzzy PID that make it much more precise,

    stable. It’s widely used in strong anti-interference and automation

     systems of mechanism, chemical industrial, chinaware, light industrial,

    metallurgy and petroleum chemical industrial. It is also applied to the

    production line of foodstuff, packing, printing, dry machine, metal

    heat process equipment to control the  temperature. simple operation.

Panel

     

 Parameter Setting

MYPIN

Indication lamp: 

       

On

: active      

Off

: inactive

AT

:               the auto-tuning operation

AL

:               the 1st alarm

OUT1:

          Heating/Main control output

OUT2/AL2

:  the 2nd control  output or the 2nd alarm

<</AT

 UNDER DISPLAY MODE,

             

a. Access/Quite auto-tuning estate (press>3s ,AT lamp ON/OFF)

            

 b. Access output preset value modification (press shortly)

          UNDER PROGRAMMING MODE,  shift the digit for modification

    

   

  Increment selected parameter value or selections

         Decrement selected parameter value or selections

SET  

UNDER DISPLAY MODE, Access programming mode

        UNDER PROGRAMMING MODE,

          

 a. Store selected parameter and index to next parameter (press shortly)

           

b. Quite programming mode (press>3s)

>>

>>

Power supply       90-260V AC/DC 50/60Hz

UNDER DISPLAYING MODE

PV displays current temperaturein F /C

SV displays preset output value

UNDER PRAGRAMMING MODE

PV displays  parameter

SV displays parameter preset value

   

  

Safety Cautions

 

Make sure the power is off before connecting the wires to avoid

      electric shock and strickly follow the connection diagram given out

       by the factory.

 ★

Make sure the power is off when cleaning the instrument

.

 ★

Make sure the instrument works under rated voltage to avoid dam

       -age or cause fire

.

 ★

Make sure the OUTPUT RELAY works at the rated load and elec

      trical life.The relay may melt or burned or even cause fire if  it works

     agains its electrical life

.

   

  

Instalation Notice

 ★

The instrument should be installed in domestic environment.Please

       pre-heat for 15 munites before use.

 ★

Ambient environment: temp:

 

0

(32F)~50

(122F),  humidity:

       35%~85%RH.

 ★

To avoid using the instrument in such environment that full of dust,

      explosive gas, vapor, or oil.

 ★

To avoid using the instrument in such environment that full of strong

      shock,high interference or other factor.

 ★

The power cable shoudn’t put together with big current cable to

      avoid electronmagnetic interference, or use another pip or shield cable.

 ★

A surge suppressor or noice filter should be installed in case of

       noice caused by equipment as motor/transformer/spiral pipe/farrite

        cores,etc..

 

 ★

The output is active after the power ON fr 10s,please consider this

      when configuring cotrol loop.

 ★

The instrument has built-in recoverable fuse to pretect from damage

     caused by short-cut circuit. It starts work automatically when

     mulfunction is removed.

 RELAY: normal open   AC 250V/3A  DC 30V/3A COS

=1

Specifications

     K         0~999℃/0~1200℃

      J         0~999℃ /0~1200℃

      T         -150~400℃ (Special order)

      S         0~1600℃

 Rt    Pt100     -199~600℃

 Cu50      -50~150℃

Input

T/C

Withstand voltage strength

Others Please mention when ordering

1500V  Rms

 (Between power terminal and the housing)

Min 50M Ω(500V DC)

(Between power terminal and the housing)

Environment temperature

Save  temperature

Environment humidity

Weight

0~50℃

-10~60℃

35~85%RH

Insulation resistance

≤ 350g

      E         0~1000℃

Consumption

   ≤ 5VA

Display range

   -199~1800℃

Accuracy

       0.3%F.S ±

2digit

Sampling cycle

   ≤ 300ms

Main output        RELAY:normal open  AC 250V/3A  DC 30V/3A COS

¢=1

SSR/LOGIC: 24V DC

±

2V/ 20mA

Alarm

SSR/LOGIC: 24V DC

±

2V/ 20mA

OUT1:  R: RELAY     S: SSR/Logic

              I: 4-20mA      V: 0-10V       N: None

Power Supply:   Default: 90-260V  AC/DC

              E: 24VDC or 18-30V AC/DC

TA

□□ - □□□□

Models

Input  signals:

    Default:TC( K,J,E, S) RTD (Pt100,Cu50)

     1: 4-20mA  0-10V  0-75mV

     2: 4-20mA  0-10V  Pt100

    F: others (indicate when ordering)

AL1:  R: RELAY    S: SSR/Logic     N: None

Dimension:   4: 48H

×

48W  6: 48H

×

96W

TA series of temperature controller

   

  

7: 72H

× 72

W

  

8: 96H

×

48W

 

9: 96H

×

96W

OUT2/AL2:

     R: RELAY   S: SSR/Logic    N: None

>>

Press 

SET

 or      and     >3s to enter the parameter setting menu.

A: Press SET to select the parameter to be changed,

B: Press 

<</AT

 key to select one of the digits of the setting(value) for

change.

C: Press     /    to make a change.

D: Press 

SET

 to save and move to the next parameter.

NOTE: SV window display convertsion. Under display mode, press

SET

 to convert display value for 

OUT 

or 

AL1

.

>>

>>

Press        >3S

SET

 AL1(Alarm  setting)

  range:  –1999-9999

AL2   mode: The same  as AL1.

 Range: 

±

100.Display value

 PV = Measured value - PVF

Integral time range 0.1-3600.  I=OFF means

 cancel  integral  time.

AM1(Alarm mode):

0: Deviation HI alarm  1: Deviatian

LO alarm  2: Absolute value HI alarm

3: Absolute value LO alarm  4: Section

outside alarm  5: Section inside alarm

6: TC  broken alarm ,The factory setting is 2

Input signal selection  TC: K, J, T,E, S

RTD: Pt100, Cu50    The factory setting is K

AL2 set range: –1999-9999.

SET

SET

3S

Shift and flashes

Modify

Stop flashing

Confirm

Self-check

All LED on

/AT

 Temp.  unit

  Input   type

Current  Temp

Preset output  value

Max input limit

Min input limit

Power on

-

3S

3S

Proportional band (%) range 0.1-3600.

If   P=OFF, it means ON/OFF control

Proportional band (%) range 0.1-3600.

If   P=OFF, it means ON/OFF control

OUT1

AT

AL

SET

TA

/AT

PV

SV

> >

>>

>>

OUT2/AL2

Mounting and Sizes

D

B

A

E

C

G

H

Sizes

Model

TA4

TA6

TA9

TA7

 44.5+0.5   45+0.5    65    65   48   48   8    80

 43.5+0.5   91+0.5    65   115   48   96   12   80

 67.5+0.5  67.5+0.5   95    95   72   72    12  100

 91+0.5    91+0.5    115   115   96   96   12  100

 

A        B    C    D   E  F   G   H

TA8

  91+0.5   43.5+0.5   65   115   96   48   12   80

F