19
Mounting
Minimelder-R / Maximelder-R
EN
5.3.1
Power supply control unit
Verify that the product is connected to mains by means of a suitable,
permanently installed cable (for example NYM-J 3 x 1.5 mm²).
Verify that the power supply to the control unit is separately fused (16 A
maximum).
1. Route the mains cable through the left cable gland into the control unit.
2. Connect the phase to terminal L1 and the neutral conductor to
terminal N.
- The protective ground conductor (PE) does not have to be connected.
Fig 5: Electrical connection
J1
5
1
6
2
4
3
1. Mains fuse F1
2. Relay fuse F2
3. Supply voltage
4. Relay for additional equip-
ment
5. Floating probe
6. Slot for EnOcean® wire-
less module
J1 jumper
5.3.2
Connecting the floating probe
1. Install the probe cable.
2. Route the probe cable through the cable gland at the right to the termi-
nals designated "Sonde".
3. Connect the two wires. Any polarity is permissible.
Summary of Contents for Maximelder-R
Page 34: ...33 Anhang Minimelder R Maximelder R DE 15 Anhang 15 1 EU Konformitätserklärung ...
Page 67: ...33 Appendix Minimelder R Maximelder R EN 15 Appendix 15 1 EU Declaration of Conformity ...
Page 100: ...33 Annexe Minimelder R Maximelder R FR 15 Annexe 15 1 Déclaration de conformité UE ...
Page 133: ...33 Appendice IT Minimelder R Maximelder R 15 Appendice 15 1 Dichiarazione di conformità UE ...
Page 134: ...34 Appendice IT Minimelder R Maximelder R ...
Page 144: ...10 Opis produktu PL Minimelder R Maximelder R 4 2 Wymiary 60 mm 65 mm 100 mm 188 mm 166 mm ...
Page 167: ...33 Aneks Minimelder R Maximelder R PL 15 Aneks 15 1 Deklaracja zgodności UE ...