APPLICATION

DESCRIPTION

APPROVALS AND CERTIFICATES

Drawing 1. Construction

4-way rotary mixing valves are commonly used with solid fuel boilers, as mixing valves which simultaneously increase 

the temperature of the water returning to the boiler. They can be also successfully utilized in systems with cast iron 

gas or oil boilers.

4-way rotary mixing valves ARV ProClick with inner threads are made of brass. The connections have octagonal shape. 

The valves have knobs for manual operation and rotation angle limiters. The scale on top of the knob is printed on one 

side with “from 0 to 10” and on the other “from 10 to 0”, so one can mount the valve in various positions. The thicker 

knob part shows the sleeve position inside the valve. The knob itself is made from a non-slip material. The durable 

plastic parts under the knob are used to mount the ARM ProClick actuator on the valve. The ProClick system does not 

require any tools. ARV ProClick valves require low torque.

The rotary mixing valves ARV ProClick comply with the Pressure Directive PED 2014/68/EU and according to article 4.3 

(sound engineering practice) must not wear the CE mark.

DN20 ÷ DN25

DN32

DN40 ÷ DN50

4-way rotary mixing valves 

ARV ProClick 

 

Art.-No 13 482 10, 13 484 10, 13 485 10,  

             13 486 10, 13 487 10

INSTRUCTION MANUAL

953.001.0064 1

TECHNICAL DATA

Parameter / piece

Value / description

Working temperature

5-110˚C

Working pressure

max 10 bar

Differential pressure

max 1 bar

Body

brass CW617N

Sealing

EPDM

Leak rate (

Δ

p=50 kPa)

max 1,5%

Rotation angle

90˚

Required torque

max 1 Nm

Glycol concentration

max 50%

MOUNTING

Notice! 

The flattening on the spindle of the valve and on the adapter mounted on it (

Drawing 1

) indicates the middle 

of the obturator inside the valve (

Drawing 2a

 and 

2b

).

 

The ARV ProClick valve is delivered with mounted knob, blue ring and scale. Not to damage the plastic elements,  

we suggest to disassemble the scale, knob and blue limiting ring before mounting the valve. These parts are moun-

ted on latch. When having trouble with dismounting the knob, one can gently pry it up with a flat screwdriver.  

Next mount the valve in the system. When the valve is in place, set it and assemble the plastic components,  

as follows:

1. 

Determine the working range of the obturator inside the valve and the closing direction (

Drawing 2

).  

First determine the hot water inlet from the boiler, system outlet, system return and boiler return. Next set  

the obturator exactly in the middle of the system outlet  and boiler return (

Drawing 2

 - “s” axis). This means 

the valve is open in 50%. The obturator must work in the range of +/- 45˚ from that position.

2. 

Determine the closing direction of the valve and choose the right side of the scale. A 4-way valve is closed when 

the hot water from the boiler is flowing completely to the return of the boiler (

Drawing 2a

 and 

2b

 – “z” axis). 

The indicator coincides with position “0” on the scale. Depending on the exact system, closing the valve can 

mean turning the obturator left (

Drawing 2a

) or right (

Drawing 2b

). A 4-way valve is open when the hot water 

from the boiler is supplying the system outlet (

Drawing 2a

 and 

2b 

– “o” axis). The indicator coincides then with 

position “10” on the scale. Depending on the exact system, opening the valve can mean turning the obturator 

right (

Drawing 2a

) or left (

Drawing 2b

). A double-sided scale is delivered with the ProClick valves. It is printed 

“from 0 to 10” on one side and “from 10 to 0” on the other. Choose the correct side following the rule: 

 - if the valve is closed turned right (clockwise) choose the scale “from 0 to 10”, 

 - if the valve is closed turned left (counter-clockwise) choose the scale “from 10 to 0”.

3. 

Put on and latch the blue limiting ring on the valve, which was set according to point 1. The indicator should 

point directly on the middle of the flattening on the spindle and adapter (

Drawing 3

). 

4. 

Lock the knob on the adapter. It fits only in one position (

Drawing 4

).

5. 

Put the lid with the chosen scale (

Drawing 5

) on the knob. To lock the lid first put the smaller inset in the hole 

inside the knob and then press the lid down.

6. 

Check if the valve works properly.

valve body DN40-DN50

valve body DN32

valve body DN20-DN25 with plastic part for 

ProClick actuator 

adapter with f attening, for 

ARM ProClick actuators 

adapter f xing screw 

knob with a thicker part showing the valve sleeve position

double-sided scale

limiting ring with indicator

f attening on the valve spindle