29
Commissioning
AFA 11
EN
6.3
Performing the function test
At the photoelectric probe
At low temperatures and in the case of liquids with a high viscosity, the liquid
may not be able to drip off completely. This may cause continuous alarm.
Verify that the liquid to be detected is detected at all temperatures that
may be present at the installation site.
1. Submerge the probe into the liquid to be detected.
- The red LED lights up and the audible alarm sounds.
2. Press the acknowledge key at the control unit.
- The audible alarm is switched off.
- The red LED lights.
3. Remove the probe from the liquid.
- The red LED goes off.
If a continuous alarm is triggered, clean the probe (see chapter "After an
alarm condition").
At the control unit
1. Press the Test key
- The red LED lights up and the audible alarm sounds.
2. Release the Test key to terminate the function test at the control unit.
Function test power outage
1. Disconnect the mains voltage.
- The red LED goes off.
- The green LED goes off.
- The audible alarm sounds (only if a 9 Volt monobloc battery is inserted).
2. Apply mains voltage.
- The green LED is on.
Summary of Contents for AFA 11
Page 12: ...11 Produktbeschreibung AFA 11 DE 4 2 Abmessungen 60 mm 65 mm 100 mm 188 mm 166 mm ...
Page 23: ...2 3 1 4 5 22 Montage DE AFA 11 2 Schließen Sie das Signal teil ...
Page 47: ...46 Anhang DE AFA 11 15 2 EU Konformitätserklärung ...
Page 48: ...47 Anhang AFA 11 DE 15 3 Leistungserklärung ...
Page 49: ...48 Anhang DE AFA 11 ...
Page 62: ...11 Product description AFA 11 EN 4 2 Dimensions 60 mm 65 mm 100 mm 188 mm 166 mm ...
Page 73: ...2 3 1 4 5 22 Mounting EN AFA 11 2 Close the control unit ...
Page 101: ...11 Description du produit AFA 11 FR 4 2 Dimensions 60 mm 65 mm 100 mm 188 mm 166 mm ...
Page 112: ...2 3 1 4 5 22 Montage FR AFA 11 2 Fermez l unité de com mande ...
Page 141: ...11 Descripción del producto AFA 11 ES 4 2 Dimensiones 60 mm 65 mm 100 mm 188 mm 166 mm ...
Page 152: ...2 3 1 4 5 22 Montaje ES AFA 11 2 Cierra la unidad de con trol ...
Page 181: ...11 Descrizione del prodotto AFA 11 IT 4 2 Dimensioni 60 mm 65 mm 100 mm 188 mm 166 mm ...
Page 192: ...2 3 1 4 5 22 Montaggio IT AFA 11 2 Chiudere lʼunità di segnale ...