Product description
8
LAG-14 ER
3 Product description
The leak detector consists of a control unit, a probe and a container
for leak detection fluid (black LAG container).
The control unit and the probe are connected by means of a two-wire
signal cable with a maximum length of 50 m.
The probe is plugged into the top of the black LAG container. In the
case of a leak in the interstitial space, the leak detection fluid level in
the black LAG container falls. The electrode rods of the probe are no
longer submerged in the leak detection fluid. The control unit detects
the change in resistance and generates an alarm.
Fig. 1: Container for leak detection fluid (black LAG container) with
probe
a
Liquid level
d
Housing part
B
Company and approval mark
e
Electrode rods
c
Signal cable