Operation
LAG-14 ER
31
The vent hole Ø 5 mm at the neck of the black LAG container must
remain open.
The system is ready for operation.
6. Apply voltage via the on-site mains fuse.
The green pilot lamp lights up.
7. Have the specialised company certify the installation, commis-
sioning and test of the leak detector using the form in chap-
7 Operation
LAG-14 ER monitors double-walled containers (tanks). In the case of
a leak, leak detection fluid escapes and LAG-14 ER triggers an
alarm. The operation of LAG-14 ER is limited to its regular
monitoring:
•
The green pilot lamp is on.
•
The red alarm lamp is not on.
•
The audible alarm is off.
7.1
Alarm condition
In the case of an alarm, refill leak detection fluid (mixed with wa-
ter in the specified mixing ratio) up to the indicated level. If the
alarm repeats, there is a leak.
The audible alarm can be muted by pressing the Acknowledge
button. The red alarm lamp remains on.
Immediately notify the installation company.