Mounting and commissioning
22
LAG-14 ER
1
Black LAG container
2
The connection line
may not be the only
support for the black
LAG container
3
DIN 6624 double-
walled
Stored liquids dan-
ger classes A I, A II,
A III, B
6.4
Pipe installation
CAUTION
The inside walls of pipes and fittings must not be galvanised
since zinc and the approved leak detections fluids form com-
pounds which may cause deposits and lead to clogging.
Use only connection pipes and fittings whose inside walls are
not galvanised.
The connection between the container (tank) and the black LAG con-
tainer must have a steady gradient towards the tank; it must not be
possible to shut it off. All connections must be tight. The inside walls
of pipes and fittings must not be galvanised. The connection line may
not be the only support for the black LAG container, even if it con-
sists of steel. Mount the black LAG container to a nearby wall, a cabi-
net for fittings or to a support made of flat steel or steel brackets in
the manhole.