Transport and storage
LAG-14 ER
17
5 Transport and storage
CAUTION
Damage to the product due to improper transport.
Do not throw or drop the product.
Protect the product from wetness, humidity, dirt and dust.
CAUTION
Damage to the product due to improper storage.
Protect the product from shock when storing it.
Store the product packaged in this film.
Store the product in a clean and dry environment.
Protect the product from wetness, humidity, dirt and dust.
Only store the product within the permissible temperature range.
6 Mounting and commissioning
6.1
Calculation fundamentals
LAG-14 ER at underground container (tank)
The effective capacity of the black LAG container is limited by the liq-
uid level screw in the centre of the container; it amounts to 4.5 litres.
For underground containers (tanks), 1 litre of leak detection fluid is
required in the black LAG container per 100 litres of interstitial space
volume.
The black LAG container is sufficient for 450 litres of interstitial space
volume. This corresponds to containers (tanks) with a storage vol-
ume of up to 60,000 litres.
Together with additional containers with an effective capacity of 4.5
litres each, the LAG14 ER leak detector can also be used for tanks
with a greater interstitial space volume.
The additional containers are connected to each other and to the
black LAG container by means of EPDM hoses.