Maintenance
KAV
13
6.2
Function test with tester (can be performed with any tank
level)
Basic information for function test with tester
1
KAV
2
Maximum liquid level
3
Tank level above filter
cup (usually lowest
point of the system)
4
5
6
Fuel oil de-aerators
Fuel oil consumer
Tester
Fig. 6: System overview and tester
Assuming that the filter cup is usually the lowest point of the line, the
following criterion must be met for anti-siphon protection:
[p
Gauge
+ p
g,max
– p
3
] < 0
p
Gauge
is directly indicated by the pressure gauge of the tester.
p
g,max
corresponds to the hydrostatic oil column when the tank is com-
pletely filled; it is determined as follows:
p
g,max
= 0.084 bar/m x h
max
p
3
corresponds to the hydrostatic oil column with the current level; it
is determined as follows:
p
3
= 0.084 bar/m x h
3
h
max
and h
3
may have to be determined at the system using a rul-
er/yardstick.
Summary of Contents for KAV
Page 17: ...Wartung 16 KAV 4 Absperrventil schließen 5 Die Verschraubung der Filtertasse öffnen ...
Page 22: ...Anhang KAV 21 13 2 Zulassungsunterlagen ...
Page 23: ...Anhang 22 KAV ...
Page 24: ...Anhang KAV 23 ...
Page 25: ...Anhang 24 KAV ...
Page 41: ...Maintenance 16 KAV 4 Close the shut off valve 5 Open the screw connection of the filter cup ...
Page 46: ...Appendix KAV 21 13 2 Approval documents ...
Page 47: ...Appendix 22 KAV ...
Page 48: ...Appendix KAV 23 ...
Page 49: ...Appendix 24 KAV ...
Page 68: ...Maintenance KAV 19 4 Fermez la vanne d arrêt 5 Ouvrez le raccord à vis du bol de filtre ...
Page 73: ...Annexe 24 KAV 13 2 Agréments ...
Page 74: ...Annexe KAV 25 ...
Page 75: ...Annexe 26 KAV ...
Page 76: ...Annexe KAV 27 ...