background image

Figure 1

Figure 1.1

1.

 

Fit the mounting element "b" to the 

valve shaft and screw the locking 

screw "c" into the valve. 

(fig 1)

.

Screw in the screw "h" to fixate the 

actuator to the valve 

(fig. 1)

.

Select one of the adjustment scales 

included with the actuator, 

corresponding to the shut-off and 

opening directions of the valve, and fit 

it to the adjustment handle of 

the actuator.
Connect the actuator as per 

corresponding wiring diagram 

(fig. 4

).

Remove the cap with the adjustment 

scale from the adjustment handle 

and fit the actuator to the valve in 

Set the mixing valve to "50% open". 

The regulating element must be 

set exactly to the centre position 

between the hot water supply and 

the cold water supply in 3-way valve

(fig. 2.1) 

and

 

exactly along the axis of 

the supply to the system and the return

to the boiler in 4-way valve 

(fig. 2.2)

.

2.

 

3.

 

4.

 

5.

 

6.

 

1. Fit the mounting element "b" to the 

    valve shaft and screw the locking 

    screw "c" into the valve 

(fig. 1)

.

    In the case of AFRISO ARV valves 

    (and in the case of most other valves), 

    mark "a" at the mounting element coincides 

    with the flat at the valve shaft; it also 

    indicates the centre position of the 

    regulating element in the valve 

    (fig. 2.1)

. You must loosen one of 

    the housing screws 

(fig. 1.1)

 so that the 

    locking screw can properly fit into the 

    ARV valves sizes DN40 and DN50.

3. Fit the actuator onto the valve. The actuator 

    is designed in such a way as to allow for 

    mounting to the valve in any position 

(fig. 2.2)

.

    The indicator element at the blue ring "g" 

    should point upwards 

(fig. 1)

. If this element 

    has another position after you have fitted the 

    actuator, pull out the adjustment handle,

    dismount the blue ring and refit it so that 

    the indicator element points upward. Then

    plug on the adjustment handle (two 

    

     

5. Fit the adjustment scale selected in section 

    4 onto the adjustment handle. The blue 

    indicator should show position "5" on the 

    adjustment scale. If the indicator has 

    a different position, the adjustment handle

    has not been fitted as required. In this case, 

    go back to section 3.

6. Connect the actuator as per wiring diagrams 

    in 

fig. 4

    A. 

3-point control:

 After you have 

        made the electrical connections, check 

        whether the actuator turns in the required 

        direction. If necessary, interchange wires 

        2 and 3. 

    B. 

2-point control:

 You can change

        the shut-off direction by changing the 

        position of the armature; dismount the

        actuator housing to access it. 

    C. 

Versions  with auxiliary switch:

 

        One of the two black wires connected to

        the auxiliary switch contacts has a red 

        connection. This wire  should be connected 

        to the phase of the controlled system. 

        If this is not the case, the red signal LED 

        will not work properly. 

    D. 

Proportion control:

 After you have made 

        the electrical connections, make the 

        following settings by means of a micro-

        switch which is accessible after you have 

        opened the actuator housing: 

    • Time for rotation by 90° (60/90/120 s), 

    • Type of control signal (U / I), 

    • Range of control signal (0..10 V / 2..10 V 

       or 0..20 mA / 4..20 mA).

2. 

3-way mixing valve:

 Determine the operating

    range of the regulating element and the 

    shut-off direction of the mixing valve and 

    then set the regulating element to 50% open 

    (fig. 2.1)

. First, determine the hot water 

    and the cold water supply of the valve 

    installed in the heating system. It should 

    be possible to move the regulating 

    element  between the hot water supply 

    and the cold water supply within a range 

    of 90°. Then adjust the regulating element 

    exactly in the centre between the hot water 

    supply and the cold water supply 

(fig. 2.1)

    During this phase, you should also 

    determine the valve shut-off direction 

    (shutting off the hot water supply) and 

    the valve opening direction (opening the 

    hot water supply).

   

 4-way mixing valve: 

Determine the operating 

    range of the regulating element of the 

    mixing valve. To do so, determine the water 

    supply from the boiler, the water supply into

    the system, the water return from the system

    and the water return to the boiler. Then adjust the

    regulating element exactly along the axis of 

    the supply to the system and the return to 

    the boiler 

(fig. 2.2) 

This corresponds to a valve

    opening of "50%". The regulating element 

    should be operated in a range of +/-45° with

    reference to this position.

4. Select the appropriate adjustment scale. 

    The actuator kit is delivered with two 

    adjustment scales: "from 0 to 10" and 

    "from 10 to 0". Hold them to the valve; 

    select the adjustment scale whose setting

    "0" corresponds to the cold water supply 

    and whose setting "10" corresponds to the 

    hot water supply - as shown in 

fig. 2.1

    You may also use another simple rule to

    select the adjustment scale.

    - If the vale is to be closed by turning to the 

      right (clockwise), select the adjustment 

      scale "from 0 to 10". 

    - If the vale is to be closed by turning to the 

      left (counter- clockwise), select the 

      adjustment scale "from 10 to 0".

 

Electrical ARM Actuator

 

 

1

2

4

3

CAUTION!

The ARM actuator may only be installed, commissioned and dismounted by properly trained 

staff. Only trained electricians may perform work on electrical circuits.

Any changes and modifications made by unauthorized staff may cause hazards and 

are prohibited for safety reasons.

Depending on the version, the ARM actuator can be operated with 

a mains voltage of 230 V. Mains voltage can cause severe 

injuries or death.
The actuator must never come into contact with water.

Disconnect the supply voltage before opening the actuator.

No modifications whatsoever may be made to the actuator.

Mounting the actuator to the mixing valve

Mounting instructions

Detailed mounting description

The ARM actuator is factory-set to 50 % open (position "5" on the adjustment scale at the 

adjustment handle). The mixing valve must also be set to a position of 50 % open so that the

actuator can be properly mounted to the valve. For this purpose, the regulating element must 

be set exactly to the centre position between the hot water supply and the cold water supply 

in 3-way valve and exactly along the axis of the supply to the system and the return to the 

boiler in 4-way valve, after you have mounted the mounting element to the valve shaft and 

tightened the locking screw. After you have set the mixing valve as described above, the valve 

and the actuator are ready for mounting.

mark

mounting element

 

locking screw

 

actuator

adjustment scale

adjustment handle

blue ring with indicator element

 

   

 

fixing screw actuator

 

 

 

fixing screw housing

selector manual mode

Page

instrukcja prosta do pudelka.indd   1

11-04-05   10:50

 

Shut-off 

direction

Cold water

Hot water

0

1

3

5

79

0

1

Figure 2.1

a

b

c

 

 

 

0

1

3

5 7 9

0

1

 

Shut-off 

direction

Hot water

Cold water

a

d

i

g

f

h

e

c

j

b

Supply from 

the boiler

 

Shut-off 

direction

 

         

10

9 7

5 3 1

0

Re

tu

rn t

th

e b

oil

er

Su

pp

ly t

                   t

he s

ys

te

 

Return from 

                   the system  

Figure 2.2

    notches at the circumference of the 

    adjustment handle should be positioned 

    horizontally) and screw in fixing screw 

    "h" 

(fig. 1)

such a way that the locking screw is 

positioned one of the several grooves 

at the rear wall of the actuator.

Four-way

Three-way

Reviews: