Technical specifications
12
Europress
Parameter
Value
Relay fuse
T 2 A
Operating pressure in
interstitial space
Approx. 530 mbar
Switch point Alarm On
465 to 485 mbar
Switch point Alarm Off
510 mbar (point of reference, results
from switching hysteresis)
Switch point Pump On
500 mbar (point of reference, results
from switching hysteresis)
Switch point Pump Off
520 to 540 mbar
Safety valve opens
≥
570 mbar
Connecting hose
PVC hose 6 x 2 mm
Length of connection lines Max. 50 m
Temperature range
Ambient
-5 °C to +50 °C
Storage
-10 °C to +60 °C
Voltage supply
Nominal voltage
AC 100-240 V ± 10 %
Rated power
< 10 VA
Electrical safety
Degree of protection
II
Protection IP
30
Mode of operation and
additional mode of opera-
tion
Type 1.B
Electromagnetic compatibility (EMC)
Interference
According to CISPR 22
Noise immunity
According to EN 61000
4.1
Approvals, tests and conformities
Europress HV complies with the EMC Directive (2004/108/EC), the
Low Voltage Directive (2006/95/EC), the Construction Products Di-