Parameter Level 0 (rolling progression of the parameters)
Table 6:
Parameter Level 0
Parameter Display
Erklärung
A
A parameter defines the amplitude (out-
put voltage) as a percentage. The ampli-
tude moves in their value between 10 and
99 in 1s increments. 10 is the minimal set
output voltage. 99 is the maximum output
voltage set.
F
Parameter F defines the oscillation fre-
quency of the vibratory drive. The value is
adjustable between 20.0 and 99.9 in 0.1s
increments, i.e. at 20.0 2400 oscillations /
min and at 99.9 11988 oscillations / min
are generated. (Mains frequency inde-
pendent)
SA
Parameter SA defines the set soft-start
ramp of the vibratory drive. The value is
between 0.1 and 2.9 seconds. The step
size is 0.1 seconds. The output voltage
runs after activation of the vibratory drive
from 0V AC linearly to the set amplitude
value within the set time SA.
SS
Parameter SS defines the set soft stop
ramp of the vibratory drive. The value is
between 0.1 and 2.9 seconds. The step
size is 0.1 seconds. The output voltage
runs after deactivation of the vibratory
drive from the set amplitude value linearly
to 0 V AC within the set time SS.
AE
AE parameter defines the setpoint for the
system. The value can be set to P, U, I,
F. P defines setpoint via an external po-
tentiometer-meter (recommended 10K
linear) U defines setpoint via external
voltage 0 - 10 V DC
I
defines setpoint via external power
4 - 20 mA DC
F
defines setpoint its own keypad
Note: If no external connection require-
ments be technically available, the sys-
tem will stop responding, external input
should be programmed and set.