background image

14

Note: 

Once the tubing has been pushed into the nut it cannot 

be pulled out. The nut will need to be removed. See Figure 14 
for correct assembly.

1.  Hand tighten the nut until the connection is tight. 

 
 
 
 
 
 
 
 

Figure 14   

Overflow Line Connection

In the event of a malfunction, the brine TANK OVERFLOW will 
direct “overflow” to the drain instead of spilling on the floor. 
This fitting should be on the side of the cabinet. Most tank 
manufacturers include a post for the tank overflow connector.
To connect the overflow line, locate the tubing connector on side 
of tank, Figure 15. Attach length of 1/2-inch (1.3-cm) I.D. tubing 
to fitting and run to drain. Do not elevate overflow line higher than 
overflow fitting. 
Do not tie into drain line of control unit. Overflow line must be a 
direct, separate line from overflow fitting to drain, sewer or tub. 
Allow an air gap as per drain line instructions. 
 
 
 
 
 
 

 
 
 
 
 
 
 
 
 
 
 
 

Figure 15  

Electrical Connection

 

WARNING: 

This valve and control are for 

dry location use only, unless used with a Listed 
Class 2 Power Supply suitable for outdoor use.

Note: 

There are no user serviceable parts in the AC adapter, 

motor or the control board.

All controllers operate on a 12-volt alternating current power 
supply. This requires use of the Pentair Water supplied AC adapter. 
A variety of AC adapters are available for different applications. 
These AC adapters are available from your supplier. They include:
 

AC Adapter

Input Voltage Application

Part Number

Standard 

wall-mount

120V 60 Hz

UL listed for 

dry locations 

1000811

Outdoor rated

120V 60 Hz

UL listed 

for outdoor 

installations

1235448

 
120V AC Adapters:

Make sure power source matches the rating printed on the AC 
adapter.

Note: 

The power source should be constant. Be certain the AC 

adapter is not on a switched outlet. Power interruptions longer 
than eight hours may cause the control to lose the day and time 
settings. When power is restored, the day and time settings 
must be re-entered.

 
 
Controller Location

The controllers are designed to be mounted on the valve or 
attached to a flat surface. Installations that do not provide easy 
access to the valve can have the controller mounted for remote 
operation.
A remote mount connection, PN 1256257, is available for the 
WC300 Series controller.

Drain Tubing

Drain

Overflow Fitting

Secure hose in place

Air Gap

Summary of Contents for Origins WC300

Page 1: ...Operation Manual 00947 1821 EA 03671...

Page 2: ...Valve Camshaft 16 Valve Operation 16 Disinfection of Water Conditioning Systems 16 Care and Use of your Brine Tank 17 WC300 Controller 17 Display Icons 18 Keypad Button 19 Regeneration Modes 19 WC300...

Page 3: ...water softeners shall have a rated salt efficiency of not less than 3350 grains of total hardness exchanged per pound of salt based on NaCI equivalency 477 grams of total hardness exchanged per kilog...

Page 4: ...ng skills Note Aerus assumes no liability for damage due to leakage and or improper installation Note The directional instructions left and right are determined by looking at the front of the unit Ico...

Page 5: ...the water conditioning system to ensure that a proper ground is maintained WARNING Dry location use only unless used with a Listed Class 2 Power Supply suitable for outdoor use General It is strongly...

Page 6: ...Down Button Set Button AC Adapter low voltage Input Chlorine Generator Outlet Main Motor Optical Sensor Connection Turbine Input or Dry Contact Signal Input For Future Use System Specifications Valve...

Page 7: ...Moisture The valve and control are rated for NEMA 3 locations Falling water should not affect performance The system is not designed to withstand extreme humidity or water spray from below Examples ar...

Page 8: ...265 Bypass 7 Valve 8 Brine Fitting 9 Upper Basket 10 Power Transformer 11 Distributor Tube Assy 12 Resin Tank 13 Cover Brine Tank 1 Cover 2 Brine Tank 3 Brine Valve 4 Float 5 Air Check 6 Brine Well 7...

Page 9: ...1 43 4 14 9 37 8 14 8 37 5 10 6 26 9 25 4 64 5 5 12 7 2 5 6 3 D C E F In cm Dimension 10 x 54 Tank 25 x 137 cm A 53 9 137 B 61 4 156 C 57 2 145 D 55 6 141 E 33 7 85 6 F 37 8 96 Figure 4 Equipment Inst...

Page 10: ...n Floor Drain Figure 5 Standard Basement Before Installation Cold water lines shown Soft Water Hard Water Outside Faucet Outside Faucet Bath Tub Lavatory Toilet Kitchen Laundry Tubs Pump or Meter Hot...

Page 11: ...the large hole in the brine well with the hole in the brine tank Install the overflow fitting in this hole to secure well to tank Lay cover aside for now To Assemble the Media Tank 1 Stand the tank up...

Page 12: ...any WC300 valve Non silicone grease may cause plastic components to fail over time Installation Instructions The system should be installed by someone familiar with plumbing practices The conditioner...

Page 13: ...of at least 1 1 2 inch between the end of the hose and the drain point 5 When the drain empties into an overhead sewer line a sink type trap must be used 6 Secure the end of the drain line to prevent...

Page 14: ...There are no user serviceable parts in the AC adapter motor or the control board All controllers operate on a 12 volt alternating current power supply This requires use of the Pentair Water supplied A...

Page 15: ...s the regenerant through the resin at a specific rate and rinses to the drain The resin is regenerated Repressurization Cycle C4 Pressure is balanced in the valve before continuing the regeneration Fa...

Page 16: ...ontaminate a water supply During normal use a conditioner may become fouled with organic matter or in some cases with bacteria from the water supply This may result in an off taste or odor in the wate...

Page 17: ...pse After loosening the salt pellets wait 2 hours and start a regeneration A second recharge may be needed to fully recondition the media You should only use sodium chloride pellet salt for water soft...

Page 18: ...second regeneration has been called for 12 The recycle sign is displayed flashing when a regeneration at the next time of regeneration has been called for Also displayed continuous when in regenerati...

Page 19: ...regeneration Press and hold REGEN to turn on the second regeneration immediately following the current regeneration The double regeneration is indicated by the x2 symbol being on steady During a Regen...

Page 20: ...generant setting Input system size media volume in cubic feet or liters Use UP and DOWN buttons to scroll through resin volume choices Choose the nearest volume to your actual system size Press SET to...

Page 21: ...of days desired Press SET to accept the regen frequency and advance to the next cycle Time Day Regen Time Day Salt Capacity Hardness SU MO TU WE TH FR SA DAYS Figure 27 Step 6 Amount of Regenerant us...

Page 22: ...rning on the Water Conditioner Start Up After you have performed the previous initial power up steps you will need to place the conditioner into operation Follow these steps carefully as they differ f...

Page 23: ...to the next cycle The hourglass icon will light while the camshaft is indexing There may be a pause at cycle C4 System Pause This cycle allows the water air pressure to equalize on each side of the v...

Page 24: ...d hold SET and DOWN for five seconds to view the H levels History Values Description Range H0 Resin volume initial setting value Cubic feet or liters H1 Days since last regeneration 0 255 H2 Current f...

Page 25: ...determines English or metric units 0 is English units 1 is metric units Use the arrow buttons to change this setting Press SET to accept the setting Time Day Regen Time Day Salt P Capacity Hardness S...

Page 26: ...263 268 1 18 1010154 O Ring Tank 1 7 4000584 Cover Lt Gray Indoor 1 19 1232370 O Ring Riser Tube 1 4000585 Skirt Lt Gray 1 20 1002449 Valve Drain Connection Fitting Elbow 3 4 NPT x 1 2 Hose Tubing 1...

Page 27: ...1 2 4000585 Shield Decorative Performa Logix 1 3 4000562 Distributor Basket Upper 1 4 21510 Distributor Tube Assy ABS 54 1 5 CH20902 2 Cover Shroud Lt Gray 1 6 CH20899 2 Shroud Resin Tank 54 Gray Ass...

Page 28: ...3 8 x 60 Long 1 5 CH15024 Cap Brine Well 4 Dia Caplug STP 4 1 6 CH15064 1 Brine Float w One Grommet As Purchased 1 7 CH15063 2 Air Check Assembly 1 8 BR10332 Tubing Insert Brass 2 9 CH20774 Overflow...

Page 29: ...erify that motor wire harness is connected to motor and controller module Verify that optical sensor is connected and in place Verify that motor gear has engaged cam gear If everything is connected tr...

Page 30: ...b Restricted drain line c Injector plugged d Injector defective e Valve disc 2 and or 3 not closed f Air check valve prematurely closed a Make correct setting according to instructions b Remove restri...

Page 31: ...pass valve to not in bypass position b Fully insert probe into meter housing c Remove meter housing free up turbine and flush with clean water Turbine should spin freely If not replace meter Contact d...

Page 32: ...lines or failure of the plumbing hook up Ordinary wear and tear shall not be considered a defect in workmanship or material Servicing your WC300 by parties other than an authorized Aerus representativ...

Page 33: ...Manuel d utilisation 00947 1821 EA 03671 A D O U C I S S E U R D E AU WC300...

Page 34: ...vanne de commande 48 Fonctionnement de la vanne de commande 48 D sinfection des syst mes d adoucissement de l eau 48 Entretien et utilisation de votre bac saumure 49 Contr leur WC300 49 Ic nes d affi...

Page 35: ...477 grammes de duret totale chang s par kilogramme de sel selon un quivalent NaCL 3 350 grains de duret totale chang s par livre de sel et ne pas diffuser plus de sel que ce qui est indiqu dans ses pa...

Page 36: ...ages dus des fuites et ou une mauvaise installation Note Les instructions de direction gauche et droite sont d termin es en regardant le devant de l appareil Figure 37 Ic nes figurant dans ce manuel A...

Page 37: ...sec seulement moins que l adoucisseur soit utilis avec une alimentation lectrique de classe 2 appropri e pour une utilisation l ext rieur En g n ral Il est fortement recommand que l installation soit...

Page 38: ...e cames Moteur Sortie Siphon de sol Entr e R gulateur de vidange de lavage contre courant Filtre grille de l injecteur Module de contr le R gulateur de remplissage Donn es techniques du syst me Type d...

Page 39: ...n u pour une installation int rieure Un environnement prot g est recommand Lorsque le syst me d adoucissement de l eau doit tre install l ext rieur il faut prendre en consid ration plusieurs points Hu...

Page 40: ...Vanne 8 Raccord pour le tuyau de saumure 9 Panier sup rieur 10 Adaptateur de courant 11 Ensemble de tube distributeur 12 R servoir de r sine 13 Couvercle Bac saumure 1 Couvercle 2 Bac saumure 3 Vanne...

Page 41: ...14 9 37 8 14 8 37 5 10 6 26 9 25 4 64 5 5 12 7 2 5 6 3 D C E F Po cm Dimensions R servoir 25 x 137 cm 10 x 54 po A 137 53 9 B 156 61 4 C 145 57 2 D 141 55 6 E 85 6 33 7 F 96 37 8 Figure 40 Installatio...

Page 42: ...ous sol normal avant l installation Tuyauterie d eau froide illustr e Eau douce Eau calcaire Robinet d ext rieur Robinet d ext rieur Bain Lavabo Toilette Cuisine Cuve de lessivage Pompe ou compteur So...

Page 43: ...lignez le gros trou du puits de saumure avec le trou du bac saumure Installez le raccord de trop plein dans ce trou pour fixer le puits au bac Mettez le couvercle de c t pour le moment Pour assembler...

Page 44: ...que WC300 Une graisse sans silicone peut causer une d faillance des composants en plastique au fil de temps Instructions d installation Le syst me doit tre install par une personne ayant des connaissa...

Page 45: ...u et le siphon de sol 5 Lorsque le syst me de vidange se vide dans une conduite d gout au dessus un siphon de type vier doit tre utilis 6 Fixez solidement l extr mit du tuyau de vidange afin de l emp...

Page 46: ...e pour une utilisation l ext rieur Note Il n existe aucune pi ce r parable dans l adaptateur CA le moteur ou le module de contr le Le contr leur fonctionne sur une alimentation en courant alternatif d...

Page 47: ...d place le r g n rant travers la r sine un taux pr cis et les impuret s sont rinc es en direction de l gout La r sine est r g n r e Repressurisation Cycle C4 La pression est quilibr e dans la vanne av...

Page 48: ...adoucissement de l eau ne favorisent pas la croissance bact rienne et ces mat riaux ne contamineront pas l approvisionnement en eau En utilisation normale un adoucisseur peut s encrasser avec de la m...

Page 49: ...s effondreront Apr s avoir desserr les pastilles de sel attendez 2 heures avant de commencer une r g n ration Une deuxi me recharge peut tre n cessaire pour remettre en tat la mati re filtrante N util...

Page 50: ...alement utilis dans la programmation de niveau II pour indiquer si le param tre affich sera verrouill l ic ne clignotera lorsque le contr leur est en niveau I 11 Lorsque x2 est affich une deuxi me r g...

Page 51: ...deuxi me r g n ration imm diatement apr s la r g n ration actuelle La duplication de r g n ration est indiqu e par le symbole x2 affich en continu Pendant une r g n ration Une valeur C est affich e p...

Page 52: ...ectionnant un param tre de r g n rant diff rent Entrez la taille du syst me volume de la mati re filtrante en pieds cubes ou en litres Utilisez les touches HAUT et BAS pour faire d filer les choix de...

Page 53: ...e clignoter le 0 Utilisez les touches HAUT et BAS pour changer le nombre de jours souhait Appuyez sur la touche R GLAGE pour accepter la fr quence de r g n ration et proc dez au param tre suivant Dure...

Page 54: ...UE VEN SAM JOURS Figure 66 Mettre l adoucisseur en fonctionnement ouvrir le robinet D marrage de l adoucisseur Apr s avoir effectu les tapes de d marrage initial pr c dentes mettez l adoucissement en...

Page 55: ...ote Il y aura un l ger retard entre chaque cycle lorsque vous avancez au cycle suivant L ic ne sablier s allume lors de l indexage de l arbre cames Il peut y avoir une pause au cycle 4 Pause du syst m...

Page 56: ...ion ou filtrage de lavage contre courant Capacit du syst me affichage uniquement Acc der aux valeurs historiques Le contr leur comporte une fonction qui fait appara tre l historique de l utilisation d...

Page 57: ...de la r g n ration P4 Nombre de jours entre r g n ration P5 Non utilis P6 Quantit de sel utilis e par heure de r g n ration ou filtrage de lavage contre courant P7 Capacit du syst me P8 Duret P9 Unit...

Page 58: ...au trait e fonctionnement normal L heure est affich e et les deux points clignotent R initialiser le contr leur Pour r initialiser le contr leur 1 Appuyez simultan ment sur les touches R GLAGE et BAS...

Page 59: ...ur 1 19 1232370 Joint torique de la colonne montante 1 4000585 Jupe gris clair 1 20 1002449 Raccord de la vanne pour tuyau de vidange coude 3 NPT x 1 2 tuyau tube 1 8 1000811 Adaptateur 120 V CA 60 Hz...

Page 60: ...r d coratif Performa Logix 1 3 4000562 Distributeur panier sup rieur 1 4 21510 Ensemble tube distributeur en plastique ABS de 137 cm 1 5 CH20902 2 Couvercle protecteur gris 1 6 CH20899 2 Protecteur de...

Page 61: ...CH15024 Capuchon puits de saumure diam tre de 10 cm Caplug STP 4 1 6 CH15064 1 Flotteur de saumure avec une bague 1 7 CH15063 2 Ensemble de contr le d air 1 8 BR10332 Pi ce d insertion tube en laiton...

Page 62: ...s du moteur est connect au moteur et au contr leur V rifiez que le capteur optique est connect et en place V rifiez que moteur peut d clencher l arbre cames Si tout est connect essayez de remplacer le...

Page 63: ...t pas ferm f Fermeture pr matur e de la vanne d injection d air a Effectuez un param trage correct selon les instructions b Retirez l objet bloquant le tuyau c Nettoyez l injecteur et le filtre d Remp...

Page 64: ...vanne de d rivation en position non contourn e b Ins rez la sonde enti rement dans le corps du compteur c Retirez le corps du compteur d gagez la turbine et rincez le avec de l eau propre La turbine...

Page 65: ...rrecte des tuyaux de vidange ou la d faillance au niveau des raccords de plomberie Une usure normale ne sera pas consid r e un d faut de fabrication ou de mat riel L entretien de votre adoucisseur WC3...

Page 66: ...66...

Page 67: ...67...

Page 68: ...rding the use of this product please call our toll free hotline 1 800 243 9078 in U S 1 800 668 0763 in Canada Pour de plus amples renseignements concernant l utilisation de cet appareil appelez sans...

Reviews: