* Minimum technical space, to be ensured in order for the chiller to work
properly and for possible maintenance.
ATTENTION with this space, the condenser coil can only be pulled out
from above; to pull it out from the side you must leave at least 2300 mm.
3000 mm
3000 mm
C1 - C2
2300 mm
The drawings are provided solely as examples.
VERSION °
Size
0800
0900
1000
1100
1200
1400
1600
1805
2006
2206
2406
2600
2800
3000
3200
3400
3600
Minimum technical spaces
Type of board
1
1
1
1
1
1
1
1
1
1
1
2
3
3
3
3
3
Fan
V-block
no.
2
2
2
2
3
3
3
4
4
4
5
5
6
6
6
7
7
Minimum technical spaces
A1
mm
3000
3000
3000
3000
3000
3000
3000
3000
3000
3000
3000
3000
3000
3000
3000
3000
3000
B1
mm
800
800
800
800
800
800
800
800
800
800
800
800
800
800
800
800
800
B2
mm
1100
1100
1100
1100
1100
1100
1100
1100
1100
1100
1100
800
800
800
800
800
800
C1
mm
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1150
1480
1480
1480
1480
1480
C2
mm
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
VERSION L
Size
0800
0900
1000
1100
1200
1400
1600
1805
2006
2206
2406
2600
2800
3000
3200
3400
3600
Minimum technical spaces
Type of board
1
1
1
1
1
1
2
1
1
1
2
2
3
3
3
3
3
Fan
V-block
no.
2
2
3
3
3
3
4
4
5
5
6
7
7
7
8
8
8
Minimum technical spaces
A1
mm
3000
3000
3000
3000
3000
3000
3000
3000
3000
3000
3000
3000
3000
3000
3000
3000
3000
B1
mm
800
800
800
800
800
800
800
800
800
800
800
800
800
800
800
800
800
B2
mm
1100
1100
1100
1100
1100
1100
800
1100
1100
1100
800
800
800
800
800
800
800
C1
mm
1000
1000
1000
1000
1000
1000
1150
1000
1000
1000
1150
1150
1480
1480
1480
1480
1480
C2
mm
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
VERSION A
Size
0800
0900
1000
1100
1200
1400
1600
1805
2006
2206
2406
2600
2800
3000
3200
3400
3600
Minimum technical spaces
Type of board
1
1
1
1
1
1
2
1
1
1
2
2
3
3
3
3
3
Fan
V-block
no.
2
2
3
3
3
3
4
4
5
5
6
7
7
7
8
8
8
Minimum technical spaces
A1
mm
3000
3000
3000
3000
3000
3000
3000
3000
3000
3000
3000
3000
3000
3000
3000
3000
3000
B1
mm
800
800
800
800
800
800
800
800
800
800
800
800
800
800
800
800
800
B2
mm
1100
1100
1100
1100
1100
1100
800
1100
1100
1100
800
800
800
800
800
800
800
C1
mm
1000
1000
1000
1000
1000
1000
1150
1000
1000
1000
1150
1150
1480
1480
1480
1480
1480
C2
mm
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000