SYSTEM OVERVIEW
General information
The MS management system offers advanced fan control features. MS management system requires a specific
configuration of the fan electronic driving box. This configuration can be modified to standard mode (without speed
control = ST mode) by simply moving a jumper on the electronic driving box (please refer to the technical file of the
fan for more information).
MS management system is composed of:
1 circuit-breaker 230 VAC - 2A
1 supply 230 VAC - 5 V DC
1 relay for alarm switching
1 Main module to manage from 1 up to 25 fans
1 Fan module per fan
1 or 2 digital temperature sensors (+ possibility of wind gauge or clock)
These components can be placed in an IP65 electric box (if outside) not included, and clipped on DIN rail. They
are interconnected through RJ11 wires (supplied) of about 25 cm
1
. The connection of Fan modules to the fans is
realised by the mean of four wires standard cable.
Functions of MS management system
Manages the simultaneous operation of inter-connected fans.
Manages powers and operating speeds.
Manages the hybrid operation according to the information received from the connected sensors
(temperature and / or [clock or wind]).
Reports locally defaults.
Returns default information on distant indicator that can be used in particular in the context of BMS.
1
This length allows to comply with the CEM and to limit the lost tension. It allows also to connect 2 modules located
on two appended DIN rail.
Summary of Contents for VBP+
Page 11: ...11 36 Aereco S A ...
Page 13: ...13 36 Aereco S A Temperature sensor connection only ...
Page 14: ...14 36 Aereco S A Wind gauge connection only ...
Page 15: ...15 36 Aereco S A Clock connection only ...
Page 16: ...16 36 Aereco S A Temperature sensor wind gauge connection ...
Page 17: ...17 36 Aereco S A Temperature sensor clock connection ...
Page 35: ...35 36 Aereco S A ...