MFC Series Boilers User Manual
CHAPTER 10 – MFC 8000/10000 DUAL FUEL BURNER
Page
112
of
170
AERCO International, Inc.
•
100 Oritani Dr.
•
Blauvelt, NY 10913
OMM-0104_94
12/29/2015
Ph.: 800-526-0288
GF-146
10.6 Pump
The pumps are equipped with a by-pass that separates return line and suction line.
Figure 10-8: TA3 Pump Technical Data
Pump Priming
10.6.1
WARNING!
Before starting the burner, make sure that the tank return line is not clogged. Obstructions in the
line could cause the seal located on the pump shaft to break.
The time required for this operation depends upon the diameter and length of the suction tubing.
If the pump fails to prime at the first starting of the burner and the burner locks out, wait
approximately 15 seconds, reset the burner, and then repeat the starting operation as often as
required After 5 or 6 starting operations, then allow 2 or 3 minutes for the transformer to cool.
IMPORTANT NOTE:
The priming operation is possible because the pump is already full of fuel when it leaves the
facto-ry. If the pump has been drained, fill it with fuel through the opening on the vacuum meter
prior to starting; otherwise, the pump will seize.
Whenever the length of the suction piping exceeds 66 - 98 ft., the supply line must be filled
using a separate pump.
PUMP MODEL
TA3
(RLS 300-400/E)
Min. delivery rate at 300 PSI
pressure
GPH
218
Delivery pressure range
PSI
102 - 580
Max. suction pressure
PSI
7.0
Viscosity range
cSt
3 - 75
Max. oil temperature
°F
302 (150 °C)
Max. return pressure
PSI
73.0
Pressure calibration in the factory
PSI
300
Key to Pump Model TA3
1
Suction 1/2" NPT
2
Return 1/2" NPT
3
Pressure Gauge Attachment G 1/4"
4
Vacuum Gauge Attachment G 1/4"
5
Pressure Adjustment Screw
6
By-Pass Screw