9.5 Final Calibration of the Pressure Switches
Air Pressure Switch Adjustment
9.5.1
The air pressure switch shown in Figure 9-11 is connected in differential and is activated by both
the negative pressure of the air intake and the air pressure from the fan.
Adjust the air pressure switch after having performed all other burner adjustments with the air
pressure switch set to the minimum scale position.
Adjusting the Air Pressure Switch
1. With the burner operating at low fire, adjust the pressure switch by slowly turning the relative
knob clockwise until the burner locks out.
2. Then turn the knob counter-clockwise about 20% of the set point and start-up the burner
again to ensure the set point is correct.
3. If the burner locks out again, turn the knob counter-clockwise in small increments until it stops
locking out.
Figure 9-11: Air Pressure Switch and Connection
Figure 9-12: Air Pressure Switch and Connection