9
Quantum MX is a decentralised mechanical ventilation unit designed to ensure air extraction in small/
medium-sized rooms. Suitable for air discharge in the presence of long ducted system. Wall, ceiling or window
installation (fig.1).
introduction
technical sPeciFications
• Material: high quality, impact and UV-resistant ABS colour RAL 9010.
• Design front cover removable for cleaning without the use of tools.
• High efficiency mixed flow impeller to optimise quietness and efficiency.
• Single phase EC Brushless motor for energy saving, with integral thermal protection.
• Motor mounted on high quality ball bearings.
• 7 segments LED display and buttons for configuration.
• Minimum speed for continuous running, intermediate speed and maximum speed selectable as indicated
in § 3, 4 and 5.
• Option to boost from trickle through LS connection.
• Installation type selection available (through wall or ducted).
• Smart humidity control and intelligent run-on timer.
• Constant volume mode.
• Suitable for continuous running.
• The fan is double insulated: no earth connection is required.
• IPX4 degree of protection.
• Power supply 220-240V~ 50Hz
equipment operation.
•
Install the product so that the impeller is not accessible from the air outlet side as
verified by contact with the Test Finger (test probe “B” of the norm EN61032) in
compliance with the current safety regulations.
• Window installation
In case of window installation it is necessary to use the appropriate window kit,
which is not included.
Attention: do not mount the product on the window without this kit.
additional safety feature:
when the design front cover is removed, the impeller stops turning to configure
the unit. To aid the setting this feature is disabled for the first 60 minutes of operation.
Upon power-up, the unit runs at the minimum continuous speed (§ 3).
If humidistat or timer is activated, the unit runs at the intermediate speed (§ 4).
If the external switch is activated, the unit runs at the maximum speed (§ 5).
After the external switch is off, the unit continues to run at the maximum speed for the pre-set period of time,
then it returns to the selected minimum speed (or to the intermediate speed in case humidistat or run-on
timer operation is on).
NOTE: the run-on timer function is activated only if the external switch has been on for at least 3 minutes.
oPeration
The unit is equipped with a 7 segment LED display, visible by removing the design front cover, and that
illuminates by pressing any button.
888
Menu