5
1.10 Technical Data
MODEL
AZURE WHEEL 25
AZURE WHEEL 55
Air flow (m3/h)
2500
5500
Max. total rated current (A)
9
8
Max. power consumption (kW)
1,67
5
Voltage/Frequency
400 V / 50 Hz / 3 ~
400 V / 50 Hz / 3 ~
Filter class (extract / outdoor air)
ePM1 55 % (F7) /
ePM10 50% (M5)
ePM1 55 % (F7) /
ePM10 50% (M5)
Weight (kg)
285
460
Sound pressure (dB)
61
64
1.11 Disassembly and re-assembly
Before starting any disassembly or re-assembly operation, please ensure that the product is
isolated from its mains electrical supply, in order to ensure that fans cannot be run. As disassembly and re-assembly
are not part of routine maintenance, these should be carried out by qualified personnel.
Ensure the unit is voltage-free and isolated, earth and short circuit the unit, cover or shield off neighbouring live components.
Ensure that the hydraulic circuit is switched off.
Close all hydraulic shut-off valves.
Isolate all connections and ensure leak-free condition regarding oil, refrigerant
As the coil piping diameter is small, waste water can remain in the unit following normal evacuation. For safety reasons, use
compressed air to blow through the system in order to remove all remaining water.
Risk of personal injury and equipment damage!
Due to a high center of gravity, some equipment can tend to tip over and cause damage to persons and property.
When transporting the unit, carefully observe its behaviour and do not get near any possible hazardous areas.
1.12 Disposal
Before starting any operation, please ensure that the product is isolated from its mains electrical
supply, in order to ensure that fans cannot be run.
Dispose of all components and filters and disused operating materials (e.g. oil, refrigerants) in an environmentally-friendly
manner in accordance with the local codes, practices and environmental regulations.
An authorized appointed contractor specializing in waste processing must dispose of the unit or its individual components. This
appointed contractor must ensure that:
– the components are separated according to material types
– the used operating materials are sorted and separated according to their respective properties.
CHAPTER 2
INSTALLATION
2.0 Assembly
AZURE WHEEL compact devices are suitable for ceiling mounting thanks to the hanging apparatuses found on. Due to noise
level which change according to working conditions, it is recommended to install the AZURE WHEEL units in the different rooms.
Assembly should take place in such a way to enable preferably short ventilation ducts and their trouble-free connection to the unit.
Tight bends in the channel will cause high pressure drops.