Current Probes & Sensors for Power Quality Meters and Power Energy Loggers
4. SPECIFICATIONS
4.1 Electrical
NOTE:
The measurement ranges specified are for the probes and sensors.
In some cases, they may differ from the ranges that can be measured by the
instrument with which they are used with.
For complete specifications:
Refer to the product user manual that is supplied
with each compatible instrument.
Model
Measurement Range
Compatibility
AmpFlex
®
193-24-BK
(1)
24
"
(610mm)
200mA to 10kA
AC
(2)
(12,000A)
(3)
All PowerPads and PEL 100 Series
AmpFlex
®
193-36-BK
(1)
36
"
(910mm)
200mA to 10kA
AC
(2)
(12,000A)
(3)
All PowerPads and PEL 100 Series
AmpFlex
®
196A-24-BK
(1)
24
"
(610mm)
200mA to 10kA
AC
(2)
(12,000A)
(3)
8435, 8436, and PEL 105
MiniFlex
®
MA193-BK
(1)
10
"
(250 mm)
200mA to 3000A
(10,000A peak)
All PowerPads and PEL 100 Series
MiniFlex
®
MA193-BK
(1)
14
"
(355 mm)
200mA to 3000A
(10,000A peak)
All PowerPads and PEL 100 Series
J93-BK
50 to 3500;
50 to 5000 (DC only)
8333, 8336, 8435, 8436 and
PEL 100 Series
MN93-BK
2 to 240A
AC
(I >200A not permanent)
All PowerPads and PEL 100 Series
MN193-BK
5A: 0.005 to 6A
AC
100A: 0.1 to 120A
AC
All PowerPads and PEL 100 Series
MR193-BK
10 to 1000A
AC
;
10 to 1300A
PEAK AC+DC
All PowerPads and PEL 100 Series
SL261
100mV/A: 100mA to 10A peak
10mV/A: 1 to 100A peak
All PowerPads and PEL 100 Series
SR193-BK
1 to 1200A
AC
(I > 1000A not continuously)
All PowerPads and PEL 100 Series
(1) 10 to 6500A
AC
for Model 8435; 100mA to 6500A for Model 8436
(2) 200mA to 10,000A measurement range for the PEL 100 Series.
(3) 12,000A is specified for the PEL 100 Series only.
Battery: 9V Alkaline NEDA 1604A, 6LR61
Battery Life: MR193-BK - 100H typical
SL261 - 55H typical
J93-BK - 70H typical
NOTE:
Battery life is twice the typical value when using Lithium batteries