Power Quality Analyzer PowerPad
®
IV Model 8345
89
17. TECHNICAL SPECIFICATIONS
The 8345 complies with standard IEC 61000-4-30, Class A.
17.1 REFERENCE CONDITIONS
Quantity of Influence
Reference Conditions
Environmental
Conditions
Ambient temperature
23 °C ± 3 °C
Relative humidity
40 %RH to 75 %RH
Atmospheric pressure
860 hPa to 1060 hPa
Electric field
< 1 V/m from 80 MHz to 1000 MHz
≤ 0.3 V/m from 1 GHz to 2 GHz
≤ 0.1 V/m from 2 GHz to 2.7 GHz
Magnetic field
< 40 A/m DC (earth's magnetic field)
< 3 A/m AC (50/60 Hz)
Instrument
Configuration
Voltage ratio
1
Current ratio
1
Voltages
Measured (not calculated)
Current sensors
Real (not simulated)
Auxiliary power supply voltage
230 V ± 1 % or 120 V ± 1 %
Instrument warm up
1 h