ST
AR
TUP MANUAL
1 Startup Manual
ECU-P1761
4-ch Isolated Digital Input, 4-ch Isolated Relay Output with IRIG-B Board
Packing List
Before installation, make sure that you have the ECU-P1761
suit which includes the card and panel as below.
Diagram
The ECU-P1761 supports the following specifications:
• Connector: 120-pin connector for UNO-4673A/4683/ECU-
4784
• BUS Interface: PCI
• Dimensions: 5.3’’ x 6.0’’ (136 x 150 mm)
• Power Requirements: 5V @ 150mA (typical); 3.3V @
60mA (typical)
• Certification: CE, FCC, IEC-61850-3 Compliant
Digital Input
• Channels:
4
• Connector:
Terminal Block
• Input Type:
Wet Contact (Sink)
• Input Voltage:
Logic 0: 0~10V; Logic
1:
30~48V
• Response time:
1 ms
• Isolation Voltage:
2,500 VDC
Relay Output
• Channels
4
• Connector
Terminal Block
• Output Type
Relay; 1 Form C
• Relay Output Voltage
250 VAC/VDC
• Max. Switching Voltage
400 VAC
• Relay Output Current:
25
°
C 3A,70
°
C, 1A
• Operate/Release Time:
Max. 8ms
• Isolation Voltage:
2,500 VDC
IRIG-B
• IRIG Interface
BNC
• Precision
1ms
• Resolution of time
1s
• Message Syntax
YYYYQQQHHMMSS
(year, day, hour,
minute&
second)
Installation
The ECU-P1761 is an expansion card for ECU-4784 which
has 2 expansion slots and UNO-4673A/4683 which has 3
expansion slots. ECU-P1761 can be plugged into any of the
slots. Follow these steps to integrate into ECU-4784/UNO-
4673A/4683.
1. Select one of the slots: unscrew the two screws on the
blank panel of the slot then remove the blanking plate.
2. Plug the ECU-P1761 into the selected slot of ECU-4784/
UNO-4673A/4683 carefully and fix it by the two screws
on the panel.
Notes
For more information on this and other Advantech products, please
visit our websites at:
http://www.advantech.com
http://www.advantech.com/eAutomation
For technical support and service:
http://www.advantech.com.tw/eservice
This manual is for ECU-P1761
Part No: 2003P17600
1st Edition
June 2016
If anything is missing or damaged, contact your distributor or
sales representative immediately.
Specifications