Before you begin, be sure 

you have 

the following:

Model BB-485LDRC9

RS-422/485 Converter, Industrial

Fast and easy on the web:

 

www.advantech.com 

+ Model BB-485LDRC9 Serial Converter
+ Required, but not included:

 

- Power Supply

 

- RS-232 Cable

 

- RS-422/485 Cable

 

QUICK START

GUIDE

Timing Issues? 

(Usually applies when using RS-485 2-wire)

Model BB-485LDRC9 uses RC time constant. This means that, when 

you are setting the DIP switches for the “baud rate”, you are setting a 

turnaround time, not a “baud rate”.

Sometimes, the turnaround time on an RS-485 2-wire device does not 

match the turnaround time that is set on the BB-485LDRC9 converter, 

even though they are both set for the same baud rate. Refer to the 

chart in Step 3 to match the turnaround time of your RS-485 2-wire 

device. If you do not know the turnaround time of your device, you can 

do the following:

 

 • Keep your device at its current baud rate, but change the 

“baud rate” on the BB-485LDRC9. Set it for one or two steps 

above or below the baud rate of your device until you get 

communication.

  • Alternatively, you can use Model BB-485DRCi-PH instead of  

the BB-485LDRC9. Model 485DRCi-PH uses bit-wise control 

so you do not have to worry about matching the timing of your 
device.

Note: Do Not use the shield drain wire as the Signal Ground between 

RS-422/485 devices. RS-422/485 systems may communicate 

successfully without the Signal Ground when nodes are located 

close together and circuit grounds for all nodes are at the same 

potential – e.g., a controlled lab environment. However, this practice 

is not recommended. If a Signal Ground is not used when nodes 

are separated by distance, and there is the possibility of lightning 

and/or other electrical noise, the common mode voltage can rise to 

levels that could compromise communications, or even damage the 

transceivers in the system nodes.

Troubleshooting

8

UL Installation Information 

Underwriters Laboratories Conditions of Acceptability

– When installed in the end-use equipment, consideration should be 

given to the following:
1.  The wiring terminals are suitable for factory wiring only.
2.  This device is to be mounted in a suitable enclosure in the end-

product.

3.  This device is suitable for operation at a maximum surrounding air 

temperature as described in the documentation. 

4.  These devices are intended for use in a Pollution Degree 2 

environment.

•  Input Voltage: 10 – 30 VDC

•  Input Power: 0.5 Watts

•  Wire Range: 12 – 24 AWG

•  Tightening Torque: 4 kgf-cm

•  Temperature Rating of field installed conductors is 105 °C 

minimum, sized for 60 °C ampacity. 

•  Use copper wire only.

•  Maximum surrounding ambient air temperature 80 °C. 

UL Installation Information

9