background image

User Manual

ADAM-4572, 
EKI-1221,EKI-1222, 
EKI-1224, EKI-1221D, 
EKI-1222D

1/2/4-port Modbus Gateway

Summary of Contents for ADAM-4572

Page 1: ...User Manual ADAM 4572 EKI 1221 EKI 1222 EKI 1224 EKI 1221D EKI 1222D 1 2 4 port Modbus Gateway...

Page 2: ...nstallation Advantech assumes no liability under the terms of this warranty as a consequence of such events Because of Advantech s high quality control standards and rigorous testing most of our custo...

Page 3: ...easonable protection against harmful interference when the equipment is operated in a commercial environment This equipment generates uses and can radiate radio frequency energy and if not installed a...

Page 4: ...ever pour any liquid into an opening This may cause fire or electrical shock 13 Never open the equipment For safety reasons the equipment should be opened only by qualified service personnel 14 If one...

Page 5: ...1221 14 Figure 2 6 Top View of EKI 1221 14 Figure 2 7 Front View of EKI 1222 15 Figure 2 8 Side View of EKI 1222 15 Figure 2 9 Back View of EKI 1222 16 Figure 2 10Top View of EKI 1222 16 Figure 2 11F...

Page 6: ...8Wiring RS 422 Connection 31 Chapter 3 Configuration 33 3 1 Installing the Configuration Utility 34 3 2 Starting the Configuration Utility 37 3 3 Discovering Modbus Gateways 38 3 3 1 Auto Searching 38...

Page 7: ...Chapter 1 1 Introduction...

Page 8: ...hrough a dual Ethernet connection the EKI 122X series greatly improves the device connectivity reliability increase system stability and simplify the redundant configuration The Modbus RTU and Modbus...

Page 9: ...EKI 1221 or EKI 1222 or EKI 1224 Modbus Gateway 1 x 6P power connector 1 x Document and software CD 1 x DIN rail kit 2 x Wall panel mount kit EKI 1221D 1222D 1 x EKI 1221D or EKI 1222D Modbus Gateway...

Page 10: ...ADAM 4572 EKI 122X Series User Manual 4...

Page 11: ...Chapter 2 2 Getting Started...

Page 12: ...s such as protocol conver sion between serial Modbus ASCII or Modbus RTU and networked Modbus TCP Modbus devices or it can be used to bridge Modbus serial devices over TCP IP net work The Modbus RTU a...

Page 13: ...tains fields confirming the action taken any data to be returned and an error checking field If an error occurred in receipt of the message or if the slave is unable to perform the requested action th...

Page 14: ...hin and transported over TCP IP based networks Modbus TCP is just as simple to implement and flexible to apply as the original Mod bus RTU The Modbus TCP protocol is defined by its form of encapsulati...

Page 15: ...2 Flow Control RTS CTS XON XOFF Speed 50 bps to 921 6 kbps Signals RS 232 TxD RxD RTS CTS DTR DSR DCD RI GND RS 422 Tx Tx Rx Rx GND RS 485 Data Data GND Protection 15 KV ESD for all signals Software...

Page 16: ...ontrol RTS CTS XON XOFF Speed 50 bps to 921 6 kbps Signals RS 232 TxD RxD RTS CTS DTR DSR DCD RI GND RS 422 Tx Tx Rx Rx GND RS 485 Data Data GND Protection 15 KV ESD for all signals Software Features...

Page 17: ...2 Flow Control RTS CTS XON XOFF Speed 50 bps to 921 6 kbps Signals RS 232 TxD RxD GND RS 422 Tx Tx Rx Rx GND RS 485 Data Data GND Protection 15 KV ESD for all signals Software Features Operation Mode...

Page 18: ...y Steady on The device server has been located by utility s locating the device function Off System is not working Ethernet Orange Blinking Ethernet port is transmitting or receiving data Steady on Et...

Page 19: ...13 ADAM 4572 EKI 122X Series User Manual Chapter 2 Getting Started 2 3 2 Dimensions Units mm EKI 1221 Figure 2 3 Front View of EKI 1221 Figure 2 4 Side View of EKI 1221...

Page 20: ...ADAM 4572 EKI 122X Series User Manual 14 Figure 2 5 Back View of EKI 1221 Figure 2 6 Top View of EKI 1221...

Page 21: ...15 ADAM 4572 EKI 122X Series User Manual Chapter 2 Getting Started EKI 1222 Figure 2 7 Front View of EKI 1222 Figure 2 8 Side View of EKI 1222...

Page 22: ...ADAM 4572 EKI 122X Series User Manual 16 Figure 2 9 Back View of EKI 1222 Figure 2 10 Top View of EKI 1222...

Page 23: ...17 ADAM 4572 EKI 122X Series User Manual Chapter 2 Getting Started EKI 1224 Figure 2 11 Front View of EKI 1224 Figure 2 12 Side View of EKI 1224...

Page 24: ...ADAM 4572 EKI 122X Series User Manual 18 Figure 2 13 Back View of EKI 1224 Figure 2 14 Top View of EKI 1224...

Page 25: ...19 ADAM 4572 EKI 122X Series User Manual Chapter 2 Getting Started EKI 1221D Figure 2 15 Front View of EKI 1221D Figure 2 16 Side View of EKI 1221D...

Page 26: ...ADAM 4572 EKI 122X Series User Manual 20 Figure 2 17 Back View of EKI 1221D Figure 2 18 Top View of EKI 1221D...

Page 27: ...21 ADAM 4572 EKI 122X Series User Manual Chapter 2 Getting Started EKI 1222D Figure 2 19 Front View of EKI 1222D Figure 2 20 Side View of EKI 1222D...

Page 28: ...ADAM 4572 EKI 122X Series User Manual 22 Figure 2 21 Back View of EKI 1222D Figure 2 22 Top View of EKI 1222D...

Page 29: ...23 ADAM 4572 EKI 122X Series User Manual Chapter 2 Getting Started ADAM 4572 Figure 2 23 Front View of ADAM 4572 Figure 2 24 Back View of ADAM 4572...

Page 30: ...ADAM 4572 EKI 122X Series User Manual 24 Figure 2 25 Bottom View of ADAM 4572 Figure 2 26 Side View of ADAM 4572...

Page 31: ...the ADAM 4572 and EKI 122X series 2 4 1 Choosing the Location Due to thier innovative design ADAM 4572 and EKI 122X series can be Fixed to a panel mount Fixed to a DIN rail Panel Wall Mounting The ADA...

Page 32: ...ADAM 4572 EKI 122X Series User Manual 26 Figure 2 28 ADAM 4572 Panel Mounting Bracket Dimensions Figure 2 29 ADAM 4572 Panel Mounting...

Page 33: ...dbus data gateway when out of factory If the DIN rail kit is not screwed on the ADAM 4572 EKI 122X series please screw the DIN rail kit on the Modbus data gateway first First hang the Modbus Gateways...

Page 34: ...ADAM 4572 EKI 122X Series User Manual 28 Figure 2 32 DIN rail Adapter Figure 2 33 DIN rail Mounting...

Page 35: ...connect an alarm indicator buzzer or other signaling equipment through the power fail relay output The relay opens if power input V1 or V2 fails Open means if you connect relay output with an LED the...

Page 36: ...de user can use a crossover Ethernet cable to connect the ADAM 4572 and EKI 122X Series to the host PC s Ethernet connector For advanced model EKI 1221D and EKI 1222D provide two Ethernet ports with o...

Page 37: ...31 ADAM 4572 EKI 122X Series User Manual Chapter 2 Getting Started Wiring for RS 485 Connection Figure 2 37 Wiring RS 485 Connection Wiring for RS 422 Connection Figure 2 38 Wiring RS 422 Connection...

Page 38: ...ADAM 4572 EKI 122X Series User Manual 32...

Page 39: ...Chapter 3 3 Configuration...

Page 40: ...the Windows Run command to execute the setup program the path for the setup program on the CD ROM should be E Utility Driver SerialDeviceServerConfigurationUtility Serial_Device_ Server_Configuration_...

Page 41: ...hapter 3 Configuration 5 Carefully read the Software License Agreement and press I Agree to continue 6 The InstallShield will specify a default installation path C Program Files Advantech eAutomation...

Page 42: ...ADAM 4572 EKI 122X Series User Manual 36 7 After few minutes a message will indicate that Configuration Utility is suc cessfully installed click Finish to exit the InstallShield...

Page 43: ...pen the Serial Device Server Configuration Utility from the Windows Start Menu by clicking Start All Programs Advantech eAutomation Serial Device Server Configuration Utility The Serial Device Server...

Page 44: ...searched and display on the Serial Device Server List Area You can click on the device name to show the fea tures of the specific device Click on the before the model name e g EKI 1224 and the utility...

Page 45: ...ce name Ethernet Information and Serial Port Information In the serial port informa tion frame it displays the operation mode status and connected host IP Click on the before the device name and the u...

Page 46: ...ADAM 4572 EKI 122X Series User Manual 40...

Page 47: ...Area and re search again Don t use this function frequently or the warning message will be pop up You also can click the Search Again button on the Quick Tool Bar and the util ity will search serial...

Page 48: ...name e g EKI 1224 and the utility will expand the tree structure to show the individual device name And clink on the before the device name and utility will expand the communication interfaces on this...

Page 49: ...ses from your network admin istrator and then configure each Advantech Modbus gateway with individual IP addresses related Subnet Mask and Gateway Setting 3 5 Setting Serial Communication Parameters C...

Page 50: ...serial interfaces RS 232 RS 485 and RS 422 You can use any one of these serial interfaces according to your requirements You must also pay special attention to the wiring scheme of the EKI 122X series...

Page 51: ...ers depend on the protocol that is running on the con nected Modbus device i e Modbus ASCII or Modbus RTU Modbus ASCII Modbus RTU Flow Control The EKI 122X series provides four options None XOn XOff R...

Page 52: ...serial port Modbus Timeouts ms This option specifies the time duration in milliseconds for the EKI 122X series to wait for a response after it has issued a command while using Modbus RTU or Modbus AS...

Page 53: ...to the devices connected to this serial port and wait the reply about slave ID information Alternative option the utility allows to manual add or delete slave ID information Modbus TCP Listen Port ADA...

Page 54: ...the column Map ID Modbus Master Mode Type This option specifies whether the Modbus RTU or Modbus ASCII master device is connected to the serial port Modbus Timeouts ms This option specifies the time d...

Page 55: ...s slave device Type the IP address in the column and its slave ID range then click Add or Delete button to add or remove the slave IP list 3 6 Function Accessible Setting The EKI 122X series provides...

Page 56: ...g with serial port will be list on the right window Click Refresh button the status will be refresh once It will be auto refresh after click Auto Refresh and the time duration is depending on the set...

Page 57: ...the serial port setting including Basic Set ting and Operation Setting via sps file format 3 8 2 Locate the Modbus Data Gateway If there are many Modbus data gateways need your management you may need...

Page 58: ...ock Device Be sure to click Reset Device to restart the Modbus gateway and store your setting pass word into the memory Click Unlock Device to unlock the Modbus data gateway and you need to fill in th...

Page 59: ...8 4 Restore to Factory Default Settings The configuration utility provides this function to let you can restore the Modbus data gateway to factory default settings The confirm message will be pop up w...

Page 60: ...ep up with the ever expending world of computing You can use the update firmware function in the utility to carry out the upgrade procedure Please access Advantech s website http www advantech com to...

Page 61: ...EKI 122X Series User Manual Chapter 3 Configuration 2 Select the firmware file you want to update 3 After downloading the firmware completely click OK button and the Modbus data gateway will restart a...

Page 62: ...tions are subject to change without notice No part of this publication may be reproduced in any form or by any means electronic photocopying recording or otherwise without prior written permis sion of...