58 

 

3.3.20.3 

Style 

The way in which an output turns on in response to a particular input event can be programmed. For example, 
an output may turn on immediately, it may turn on after a delay or it may pulse for a set time and then turn on. 
This method of operation is called a Style. A style may have up to three different methods of operation. For 
example,  

Delay

 Mode, Wait

 Mode, Wait

 Mode. 

Style 00 is fixed to turn on immediately an input event occurs. 

Style 01 is fixed to pulse immediately an input event occurs. 

Styles 02 to 20 are programmable. 

Press the

 button to step on to the style field. Change the setting using number entry to select the required 

output style. If the style is already programmed elsewhere, the relevant style parameters are automatically 
entered into the appropriate fields. 

3.3.20.4 

Delay 

The delay field is the time from qualification of the input event to something happening at the output. The delay 
time can be set in intervals of 1 second up to a maximum of 250 seconds. 

Press the

 button to step on to the delay field and change the setting using number entry. 

3.3.20.5 

Mode 

The mode field defines the method of operation of the output when it is first activated. This can be ON or 
PULSE. 

Press the

 button to step on to the delay field and change the setting using the 

 button. 

Note: Pulse settings are by default 1-second ON / 1-second OFF. Other pulse options can be specified on the 
PC Tool (such as 2s ON / 3s OFF) 

– these can be assigned to on-board outputs only. 

3.3.20.6 

Wait 

The wait field is the time from first activation of the output to the next operational condition (mode) of the output. 
For example, the output could initially be delayed for 20 seconds and turn on in a pulsing mode. After a wait of a 
further 30 seconds it can be programmed to turn on differently such as ON. The wait time can be set in intervals 
of 1 second up to a maximum of 250 seconds. 

Press the

 button to step on to the wait field and change the setting using number entry. 

3.3.20.7 

Copying Output Settings to Multiple Zones 

To save time in the entry of similar Output Group Settings for each zone, it is possible to copy information 
programmed for a particular zone to subsequent zones. 

Press the 

 button to highlight the required zone number and then press the 

 button. The display shows a 

pop-up window prompting for the number of the zone to which to copy the information.  

Use the number entry to select the required zone number. The Output Group programming for all of the zones 
from the currently selected zone to the zone number entered will be programmed with the same information as 
the currently selected zone. 

3.3.21 Investigation Delays 

 

P

P

C

C

 

 

O

O

N

N

L

L

Y

Y

 

 

 

In addition to the “Cause and Effect” programming described above, the panels also support 
an “Investigation Delay Mode” which allows time for a building supervisor to investigate fire 
signals before turning outputs on. This mode can only be configured from the PC software. 

 

There are two parts to this delay. The first stage is set relatively short. If the building supervisor does not 
acknowledge the fire signal within the first stage, the delayed outputs will turn on. The second stage gives a 
longer period to investigate the fire signal. This delay can be cancelled at any time by pressing the EVACUATE 
button, or any nominated input devices (by default, all call points cancel this mode). 

Each input and output device can be individually programmed to use the investigation delay from the PC 
configuration software, together with the times appropriate to each stage of the delay.  The user manual gives 
details of how the building occupier can turn the investigation delay feature on or off. 

Summary of Contents for MxPro 5 Mx-5100

Page 1: ...www advancedco com Fire Alarm Panels Product Manual The operation and functions described in this manual are available from Software Version 5000 050 04 onwards...

Page 2: ...ine Switched Mode On board 24V DC 5A High Efficiency Off Line Switched Mode 2x On board 24V DC 5A High Efficiency Off Line Switched Mode Output Voltage1 18 0V 28 0V 18 0V 28 0V 18 0V 28 0V 18 0V 28 0V...

Page 3: ...iver Card 20 2 4 PLUG IN PERIPHERAL BUS MODULES 20 2 4 1 Routing Interface Card Plug In 20 2 4 2 2 Way Relay Card Plug In 21 2 4 3 Network Card 21 2 4 4 Peripheral Module Chassis Mounting 22 2 4 5 VdS...

Page 4: ...learn 46 3 3 3 2 Procedure if the Panel finds Devices Missing 46 3 3 3 3 Procedure if the Panel finds Devices Added 46 3 3 3 4 Procedure if the Panel finds Devices Changed 47 3 3 4 Loop Calibrate 47...

Page 5: ...OTTEN LEVEL 3 PASSWORD 63 5 2 APPENDIX 2 RECOMMENDED FIRE RATED CABLES 64 5 2 1 Detector Loop Lengths Apollo Hochiki and AV 64 5 2 2 Sounder Circuit Lengths 65 5 2 3 Fire Fault Routing Circuit Lengths...

Page 6: ...ipment Investigation Delays to Outputs Dependency on more than one alarm signal Fault Signals from Points Disablement of Points Alarm Counter Test Condition Standardised Input Output EN54 4 1997 A1 20...

Page 7: ...the 5000 5000V 5000N Series Fire Alarm Control Panels This manual provides generic programming and installation information Refer to the appropriate protocol application note for further and specific...

Page 8: ...pment Investigation Delays to Outputs Co incidence Detection Alarm Counter Fault Signals from Points Output to Fault Routing Equipment Disablement of Points Test Condition Standardised I O 7 8 7 9 7 1...

Page 9: ...tion such as the fire brigade office Requires installation of a routing interface card Refer to Sections 2 4 1 2 5 12 3 3 20 and 3 3 21 for further information Section 7 11 Delays to Outputs The C I E...

Page 10: ...supported over the Ad Net Network 1 6 Installation Approvals 1 6 1 Fire System Installations The panel must be installed and configured for operation in accordance with these instructions and the app...

Page 11: ...onto a fascia plate Key Lock Option for eight key switches or four key switches and a printer Option for a 50 Zone LED card WARNING HIGH VOLTAGE INSIDE DO NOT REMOVE COVER No Serviceable Parts Inside...

Page 12: ...splay Cable AC Input Optional Zone LED Card Optional Key Switches Door Lock Ratings Label L D Enclosures comprises Back Box Base Card with 2x Loop Drivers mounted onto a Chassis Plate Door with Displa...

Page 13: ...MXP 513 XXX LED cards fitted to door The MX 5800 consists of two independent systems comprising of 4 LP Base Cards and Display Cards only one display is normally visible and each system capable of sup...

Page 14: ...ly available rack enclosures Sarel or Rittal or in Advanced MXM 510 XXU Rack enclosures Weight 6Kg For more information on the rack system and optional modules see document 680 195 MXM 510 16U Rack En...

Page 15: ...There is no need to remove these screws fully the chassis plate has keyhole style mounting holes Carefully remove the chassis from the rear enclosure and place in a safe place to prevent accidental da...

Page 16: ...and knockouts top 427 340 299 26 183 5 183 5 Knockouts x2 271 M Enclosure Size and Fixing Point Dimensions L Enclosure Size and knockouts top D Enclosure Size and knockouts top 447 472 431 26 183 5 18...

Page 17: ...e Size and Fixing Point Dimensions 2 2 4 Remounting the Chassis Carefully replace the chassis and fix into place using the two screws Reconnect the chassis earth cable to the spade terminal in the rea...

Page 18: ...mended Fire Rated Cables for further information on cable types to be used Refer to specific sections on how to install AC Mains input and loop sounder relay and AUX outputs circuits WARNING HIGH VOLT...

Page 19: ...ower before installing or removing printed circuit boards Observe anti static precautions at all times when handling printed circuit boards A section of the Base Card identifying the locations for eac...

Page 20: ...ls of the network connections 2 4 1 Routing Interface Card Plug In Outputs to Routing Equipment Clauses 7 9 and 8 9 Output to Fire Protection Equipment Clause 7 10 The Routing Interface Card provides...

Page 21: ...uit boards 2 4 3 Network Card An Mxp 503 STD or an Mxp 509 FT Network Card can be installed onto the base card The card is fitted to the base card using 1x M3 screw and 3x plastic pillars A metal pill...

Page 22: ...ons Refer to wiring section for further information The screw fixing is essential for EMC Immunity protection WARNING HIGH VOLTAGE INSIDE DO NOT REMOVE COVER No Serviceable Parts Inside Mxp 034 Power...

Page 23: ...Chassis Isolate ALL sources of power before installing or removing printed circuit boards 2 4 5 1 Option Relay Card An optional Mxp 508 8 Way Relay Card can be mounted on top of the interface card to...

Page 24: ...into the enclosure at the upper right corner only Keep the AC wiring away from the circuit boards and all other wiring FUSE Brown Green LIVE EARTH NEUTRAL Panel Wiring Blue 3 15A AC Mains termination...

Page 25: ...of battery 1 and the Black lead to the negative terminal of battery 2 Connect the negative of battery 1 to the positive of battery 2 using the supplied link cable Ensure that the battery terminals do...

Page 26: ...7Ah 12AH batteries within the panel WARNING HIGH VOLTAGE INSIDE DO NOT REMOVE COVER No Serviceable Parts Inside 2 5 2 3 Large Enclosure The diagrams opposite show the recommended location and orientat...

Page 27: ...om 27 2 5 2 4 Deep Enclosure The diagrams opposite show the recommended location and orientation for 7Ah 38AH 45AH batteries within the panel WARNING HIGH VOLTAGE INSID DO NOT REMOVE COVER No Servicea...

Page 28: ...he multi loop panels IN IN OUT OUT Base Card Terminations Typical When screened cable is used it is vital to connect the screen drain wire to the chassis earth at the cable gland input earth stud in t...

Page 29: ...hat all segments of the cable loop have continuity of the screen and take care to ensure that the screen is not exposed to any other earth point e g metalwork cable trays junction boxes etc The sounde...

Page 30: ...onnect from the OUT socket on the first panel to the IN socket on the next panel as follows SCN B A A B SCN IN OUT To Base Card OUT Screen B A Screen B A IN STD Up to 32 nodes The IN terminals on the...

Page 31: ...outing equipment itself Not fully EN54 2 compliant 2 5 7 Auxiliary Supply Output The MxPro 5 Series are equipped with an auxiliary 24V DC 500mA power supply output This can be used for powering ancill...

Page 32: ...rovided with a slide in label pocket for a user text description The switch cable connector plugs into the display card connector as show opposite Switch Input Connector Optional Key Switches 87654321...

Page 33: ...put should be connected to and driven by another fire routing output located on a separate panel Routing Interface FIRE 1 FAULT FAILSAFE INPUT Output from another panel OUT IN OUT IN FSI OUT IN FIRE 2...

Page 34: ...configured as monitored or non monitored default If set to monitored EOL 10K Active Resistance 470 1 2 3 4 15 16 17 18 11 12 13 14 5 6 7 8 9 10 FAT FBF FSD E AUSG S red E RS232 To base card To relay...

Page 35: ...ails on how to configure program and connect specific types RS485 Connection RS232 Connection Note Units connected via RS232 must be wired in rigid conduit and located 3 metres from the panel FAT 1 2...

Page 36: ...FBF RS232 ADP N3E 0V TX RX TX RX 0V 1 2 3 4 FAT FBF RS232 ADP N3S 0V TX RX TX RX 0V PANEL 1 PANEL n AUSG AUSG V 27 V 26 UB2 UB2 SIO2 SIO2 UB1 UB1 SIO1 SIO1 UB2 UB2 SIO2 SIO2 UB1 UB1 SIO1 SIO1 UB2 UB2...

Page 37: ...panel totally lose power or be in a system fault condition the fail safe input is automatically connected to the E output The router should be provided with power from a separate power supply Router...

Page 38: ...ds refer to Section 3 3 13 Level 3 Passwords If this number is lost it is not possible to enter commission mode functions Refer to section 5 1 for further formation Default 7654 3 1 2 Memory Lock The...

Page 39: ...so on see table below After pressing the button to obtain the required character wait for 1 second and the character will be entered and the cursor will move to the next character in the text descript...

Page 40: ...Alarms View Zones and Inputs that are reporting an alarm condition during test Disabled View Zones Inputs and Outputs that are disabled Inputs View the current state of Zones and Inputs Outputs View...

Page 41: ...in positions 1 and 2 of an Mx 5400 Press the buttons to scroll through the list of loops available and then press the button to select the loop required Note For the 5100 and as there is only one pos...

Page 42: ...dergruppe and can be in the range 1 32 Use the number keys to change the meldergruppe number assigned to the device 3 3 2 5 Device Text This parameter shows the 26 character location text assigned to...

Page 43: ...efer to the appropriate protocol application note for further information This parameter shows if the device sensitivity is set to its DEFAULT or CUSTOM settings For example Loop 1 Devices More Addres...

Page 44: ...Alarm 55 Mode 5 Pre Alarm 40 Delay 5s Min Value 8 SAM SSM In the above example the panel is using special sensitivity mode 5 and time clock number 2 Enter 0 in the SSM Clock field to cancel Special S...

Page 45: ...o check the chamber response and illuminate the detector LED and individual outputs sounders and relays can be tested to check output connections and operation While the address field is highlighted p...

Page 46: ...into the panel the Auto Learn process is suspended and the display shows a pop up window with options For example KEEP THIS DEVICE DELETE THIS DEVICE KEEP ALL MISSING DELETE ALL MISSING Address 002 DE...

Page 47: ...ACCEPT NEW DEVICE KEEP OLD DEVICE ACCEPT ALL NEW DEVICES REJECT ALL NEW DEVICES Address 002 TYPE CHANGE This situation could arise for example if a heat detector has been installed in place of an opt...

Page 48: ...isabled Last Enable The date and time that the device was last re enabled Created The date and time that the device was either auto learnt at the panel or added to the device list from a PC configurat...

Page 49: ...ation of the Level 3 password For example Commission Menu 1 Please Enter Your Password Next Menu If the password is incorrect this will be indicated or if the password is not entered within 5 seconds...

Page 50: ...7654 3 3 14 Time and Date This function allows the time and date in the panel to be changed On entry to the function the display shows the current time and date with confirmation of the day of the wee...

Page 51: ...he View Panel option see 3 3 12 and user manual 3 3 17 Setup The Setup Options Menu enables the configuration of panel generic operating parameters When the option is selected the display shows a list...

Page 52: ...nes what type of information and to what level is stored in the Event Log There are three options STANDARD the normal operating mode logging fire alarm fault and warning conditions as they occur STAND...

Page 53: ...l selected and the checksum for the configuration data A note of this number can be taken and then checked on the next service visit to see if any changes have been made to the configuration data Setu...

Page 54: ...glass 3 3 19 Panel The Panel Menu Option shows a list of the internal panel circuits and provides a means to change their default configuration settings Only use this menu if changes are to be made to...

Page 55: ...tely flash on the loss of the AC Supply but the fault condition is only reported after the delay time default 10s has elapsed SENSITIVITY ADJUST MODE MONITOR Alarm Pre Alarm Delay 10s Min Value 372 SA...

Page 56: ...e Output Group Number field and then enter the number of the output group required using the number buttons The display always shows the Output Group is shown in the top left corner Press the buttons...

Page 57: ...rmitted to select multiple input types in which case a combination of input events will result in an output action If there is a combination of input events the CAUSE display above shows this extended...

Page 58: ...a wait of a further 30 seconds it can be programmed to turn on differently such as ON The wait time can be set in intervals of 1 second up to a maximum of 250 seconds Press the button to step on to th...

Page 59: ...a manual call point that is programmed to turn on all outputs immediately 3 3 22 Test This function is the same as User Level 2 function refer to User Manual for further information The following fun...

Page 60: ...ll entries in the logbook have been addressed check the event log in the panel and take the necessary remedial actions b Visually inspect the panel for any moisture ingress or other deterioration chec...

Page 61: ...very 10 C rise above ambient Refer to battery manufacturer for further information Manufacturer Part Numbers YUASA POWERSONIC 4AH NP4 12 5AH PS 1250 7AH NP7 12 7AH PS 1270 12AH NP12 12 12AH PS 12110 1...

Page 62: ...504 4 2 3 Spares Part Number Description MXS 501 1 LP Base Card only AP HO MXS 501V 1 LP Base Card only AV MXS 501N 1 LP Base Card only NITTAN MXS 502 2 LP Base Card only AP HO MXS 502V 2 LP Base Car...

Page 63: ...unctions entering 1 when prompted for the password As soon as the Password Invalid message is shown press the 0 button and the display will show a decryption key Make a note of the first part of this...

Page 64: ...Detector Loop Lengths Apollo Hochiki and AV 16 With the above cables loops can be up to 2Km in length However care must be taken when designing the system to take into account the maximum loop loading...

Page 65: ...ble Resistance RCABLE for 1 5mm 2 is 0 024 metre Cable Resistance RCABLE for 2 5mm 2 is 0 015 metre Insulation Resistance Core Core and Core Screen 2M 5 2 3 Fire Fault Routing Circuit Lengths The volt...

Page 66: ...n when using the Nittan protocol since the loop voltage is different to other protocols 18 Use the detector manufacturers technical information to calculate the load on the loop for both the quiescent...

Page 67: ...Output Group Assign All Sounders of Floor 6 Output Group 6 Assign All Sounders of Floor 7 Output Group 7 Assign All Sounders of Floor 8 Output Group 8 Refer to Section 3 3 2 8 for how to assign the o...

Page 68: ...FIRE 02 30s Pulse 120s 23 ANY FIRE 02 30s Pulse 120s 24 ANY FIRE 02 30s Pulse 120s STYLE 02 MODE Wait MODE On On On More Output Group 7 Sounders on Floor 7 Output Group 7 3 9 Mem used ZONE CAUSE STYL...

Page 69: ...ow to configure the panel for operation with detector LED driven base sounders Also details limitations 680 085 Software Upgrades Application Note Explains how to upgrade the software in the Graphics...

Page 70: ...f sounder devices Fire Fault Routing EN54 2 1997 Clauses 7 9 8 9 Network If provided then at least two fire and fault routing interfaces or a fail safe redundant connection shall be provided These sho...

Page 71: ...Ringing Styles 40 40 40 4026 10 10 10 Max of Output Groups 200 200 200 20026 200 200 200 Max of Output Group Lines 1150 1150 1150 115026 250 250 250 Requires PC CONFIG to define more than one line pe...

Page 72: ...www advancedco com 72 This page is intentionally left blank...

Page 73: ...www advancedco com 73 USER NOTES...

Page 74: ...vanced Electronics Ltd Moorland Way Cramlington Northumberland NE23 1WE UK Tel 44 0 1670 707 111 Fax 44 0 1670 707 222 Email sales advancedco com Web www advancedco com Doc Number 680 165 Revision 05...

Reviews: