Table 7: Reporting Summaries Continued
AX Series FACP
Event Type
DACT
Report Description
SIA
Code
Contact ID
Code
Point Trouble Reporting
Activation of:
Device Dirty
Device Trouble
Device Missing
New Device
NAC Module Trouble
NAC Module Lost
Input Module Trouble
Double Address
Type Change
EEPROM Mode
Not Ready
Too High
Too Low
Fail to Open
Fail to Close
Point Monitor Trouble
*UT pppp
1 373 nn zzz
Restoral of:
Device Dirty
Device Trouble
Device Missing
New Device
NAC Module Trouble
NAC Module Lost
Input Module Trouble
Double Address
Type Change
EEPROM Mode
Not Ready
Too High
Too Low
Fail to Open
Fail to Close
Point Monitor Restore
*UR pppp
3 373 nn zzz
Disable and Ground Fault Reporting
Disable
Point Monitor Disable
*FB pppp
1 571 nn zzz
Disable Restoral
Point Monitor Disable Restore
*FH pppp
3 571 nn zzz
Ground Fault
Ground Fault Trouble
*IA aaaa
1 310 nn 000
Ground Fault Restoral
Ground Fault Trouble Restore
*IR aaaa
3 310 nn 000