Table 6: Sys Trouble LED Indications
No. of
Flashes
Indicates Description
2 Internal
RAM Test
Failure
The internal RAM failed.
This failure can occur any
time. During failure, the
D9068P continuously cycles
through its start-up routine.
Each time the start-up
routine takes place, the SYS
TROUBLE LED flashes two
times.
Contact Advanced
Technical Support
immediately at (508) 453-
9995.
3 External
RAM Test
Failure
The external RAM failed.
This failure can occur any
time. During failure, the
D9068P continuously cycles
through its start-up routine.
Each time the start-up
routine takes place, the
SYS TROUBLE LED flashes
three times.
Contact Advanced
Technical Support
immediately at (508) 453-
9995.
4 ROM
Checksum
Failure
The ROM checksum failed.
This failure can occur at any
time. During failure, the
D9068P continuously cycles
through its start-up routine.
Each time the start-up
routine occurs, the SYS
TROUBLE LED flashes four
times.
Contact Advanced
Technical Support
immediately at (508) 453-
9995.
5 EEPROM
Checksum
Failure
An EEPROM Test is
performed every 10
minutes. If the checksum
fails, the D9068P
automatically defaults. The
SYS TROUBLE LED
illuminates and TROUBLE
PROGRAMMING appears
on the keypad. You must
reprogram all configuration
settings. If this failure
occurs often, contact
Advanced Technical
Support immediately at
(508) 453-9995.
6.2 Input
Points
6.3 Trouble
Relay
6.4 Manual Test Report Failure
If the D9068P fails to send the Manual Test Report
in two attempts or the [* Clear] key is pressed, the
report transmission is aborted. A COMM FAULT
message is not sent. The DACT-PRG Keypad
emits a three-beep tone and the message
COMMUNICATOR FAILED appears. After 2 sec,
the keypad display is updated to show CLEARING
ALL REPORTS!! Any report in the report queue,
including the Manual Test Report, is deleted. The
rotating Test Menu appears after 2 sec.
6.5 Reports in Queue
If there are any reports in the queue, the DACT-
PRG Keypad shows the message REPORTS IN
QUEUE PLEASE WAIT. The D9068P then waits
for these reports to be sent. If you press [* Clear]
on the DACT-PRG Keypad, the wait ends, the
DACT-PRG Keypad emits a three-beep tone, and
the keypad’s LCD shows the message, ERROR
DURING COMM TEST. The rotating Test Menu
returns to the keypad’s LCD after showing the
message for 2 sec.
When the report queue is empty, the D9068P
prompts you to select the telephone line to be used
(either Line 1 or Line 2). The D9068P can also
prompt you to alternate the telephone lines. For
details, refer to
1: TEST COMM
on page 40.
When the third option (
ALTERNATE
) is selected,
the telephone line is switched from the line used in
the last Manual Test Report to the other line. This
switch occurs whether you select the line number
or
ALTERNATE
. Pressing [* Clear] instead of a
selection key switches between Line 1 and Line 2.
Sending an Auto Test does not affect the phone
line sequence of the Manual Test Report. When
the line selection is complete, the Manual Test
Report is added to the report queue.
Input Points are not supported by the D9068P.
The reporting of point, zone, and network
information is handled by the AX Series FACP.
Trouble Relay operation is not used with the
D9068P. The monitoring and reporting of
D9068P troubles/faults is performed by the AX
Series FACP.