www.advancedco.com
36
5.4.4 PROG
RELAY
The D9068P operates via serial communications
from the AX Series Intelligent Fire Alarm Control
Panel, for this reason programming the trouble
relay “PROG RELAY” should not be performed.
The monitoring and reporting of D9068P
troubles/faults is performed by the AX Series
FACP.
5.4.5 PROG
ACC’NTS
The
PROG ACC’NTS
feature allows you to
program parameters for event reporting.
To program parameters for event reporting:
1. At the Programming Menu, press [5] to select
5: PROG ACC’NTS
.
2. Press the number key that corresponds to
your selection. Refer to the following
sections for account programming
information.
1: ACCOUNT NUMS
To access
ACCOUNT NUMS
, select
[0]:
PROGRAM
--->
[5]: PROG ACC’NTS
--->
[1]:
ACCOUNT NUMS
.
The account numbers identify the D9068P when it
reports to the central station. To use account
numbers to identify the D9068P when reporting the
central station:
1. At the
PROG ACC’NTS
Submenu, press [1] to
select
1: ACCOUNT NUMS
. The window
shows:
2. Press the number that corresponds with the
account number you want to set. The window
shows:
3. The existing number appears on the top line.
Access hexadecimal digits A through F by
pressing [Test]. Press [1] for A, [2] for B, [3] for
C, [4] for D, [5] for E, and [6] for F.
4. Enter the new number on the second line and
press [#] to verify your entry.
5. Press [* Clear] to return to the Prog Acc’nts
Submenu.
6. Program Account Number 2 using the same
procedure.
2: PHONE NUMS
To access
PHONE NUMS
, select
[0]: PROGRAM
--->
[5]: PROG ACC’NTS
--->
[2]: PHONE NUMS
.
The system can be programmed with two reporting
phone numbers. Use Phone Number 1 with
Account Number 1 and Phone Number 2 with
Account Number 2. Remote programming occurs
on Phone Line 1 using Phone Number 3.
• PHONE #1 is Phone Number 1.
• PHONE #2 is Phone Number 2.
• PHONE #3 is Phone Number 3. This phone
number is not available at this time. It is
reserved for future use.
PROG RELAY should not be performed. The
monitoring and reporting of D9068P
troubles/faults is performed by the AX Series
FACP.
0000 is not a valid account number. At least
one of the digits must be non-zero.
Use both telephone numbers to comply with
UL and NFPA standards.