2.5 Connecting the DACT-PRG LCD Keypad to the AX-SEB Module
Use the DACT-PRG LCD Keypad to program the D9068P DACT
Carefully pry the back cover of the DACT-PRG LCD Keypad off and wire the provided five (5) wire harness (wire
colors; red, two blacks, green, and yellow), with a Molex connector on one end, to the DACT-PRG LCD keypad.
See figure 10
With the back cover still removed confirm that the DACT-PRG LCD Keypad address is set to 1. If not, set the
address by placing one of the provided black jumpers across pins one and two. This will set the address to 1. See
figure 10
Once wired and addressed correctly, the DACT-PRG LCD keypad is capable of being used to program the D9068P
DACT. To program the D9068P DACT simply plug the keypad Molex connector into the AX-SEB connector labelled
Keypad/PL3, located on the lower right corner of the AX-SEB PC board.
3 D9068P Start Up
This section describes the proper sequence of events pertaining to the D9068P DACT when the AX Series
Intelligent Fire Alarm Control Panel is first powered up.
R
B
G
Y
DACT-PRG
LCD Keypad
To PL3
Keypad Connector
on AX-SEB
Figure 10 – DACT-PRG LCD Keypad Wiring and Addressing
1 2 4 8
DACT-PRG
Addressing
While utilizing the DACT-PRG LCD Keypad if no keypad activity occurs for 3 minutes, the DACT-PRG
LCD Keypad’s access will be disabled. When disabled the keypad’s buzzer will sound and a SYSTEM
FAULT message will appear on the DACT-PRG LCD display. To re-establish communications with the
D9068P DACT, simply disconnect the DACT-PRG Molex connector from the AX-SEB and reconnect it.
While the DACT-PRG LCD Keypad is connected and being utilized to program the D9068P, the D9068P
does not monitor the connection to the AX Series serial port.