Advanced 56000-005ADV Installation Instructions Download Page 1

4

1

ADVANCED FIRE SYSTEMS INC.

100 South Street • Hopkinton, MA 01748

Telephone: (508) 453-9995 

www.afsi.us.com

56000-005ADV 

Dual Action Addressable  

Manual Polycarbonate Pull Station 

Installation Instructions 

The Dual Action Polycarbonate Addressable Manual Pull Station may be flush 

mounted on a single gang electrical box, or it may be surface mounted using the 

Pull Station Polycarbonate Back Box (56000-006, sold separately). Be sure to follow 

local codes and regulations. To comply with ADA standards, the Pull Station must be 

connected less than 48 inches above floor level for front wheelchair access, and less 

than 54 inches for side wheel chair access.

Control Panel Compatibility

Compatibility Identifier number: 56000-005ADV. The module has been approved 

by Underwriters Laboratories Inc. The pull station is compatible with Advanced Fire 

Systems Inc's AX Series fire control panels. Contact Advanced Fire Systems Inc or refer 

to the Fire Alarm Control Unit's installation manual for more details.

Set the address using the DIP switches in accordance with the address table overleaf.

Open the Pull Station using the included key, turning the key to the right and allowing 

the Pull Station to open out.

With the Pull Station open, carefully undo the clear protective cover to the circuit 

board area. The cover should open out, hinging from the bottom, closest to the 

alarm switch.  If the clear protective cover comes off completely, replace the cover 

by making sure that the protruding pivot points are positioned down, toward the 

alarm switch, and aligned with the corresponding slots. 

Program the address of the station using the DIP switches under the clear protective 

cover.  When address programming is completed, apply equal pressure over the 

upper tabs of the cover until it snaps into place and is secure.

See Fig 1 for wiring options.

If using the Pull Station Polycarbonate Back Box (56000-006), attach to the wall 

using four #8 screws that are appropriate for the wall type or anchor. Verify that the 

orientation of the box is as shown in Figure 1 on the following page, with the arrows 

inside the box pointing UP. Connect the ½ NPT conduit to the top or bottom of the 

box and run the wiring as required by the application. Make sure that the wires at the 

back of the pull station are not pinched by the electrical box during installation.

Close and lock the station using the key provided. Test the station as required by the 

local code and the particular installation. 

Reset the station by opening and closing it.

APD0519 A130107

Analog Value

 

AV=4:   Trouble

 

AV=16 

Normal

 

AV=64:  Alarm State

Unit generates priority interrupt.

Technical Data

Operating voltage 

17-28V DC

 

UL listed to operate 

20-28V DC

Current Consumption at 24V

Stand by current 

200µA

LED Operated Alarm current 

3.6mA + Quiescent

Output Bit

Function

Input Bit

Function

2

LED         1 = On

                0 = Off

2

LED Confirmed    1 = On

                               0 = Off

1

TEST         1 = On

                0 = Off

1

1 in normal state

0 in alarm state

0

Not Used

0

0 in normal state

1 in alarm state