Operating the Arc Fault
Detection Unit
GENERAL DESCRIPTION
The Arc Fault Detection Unit (ADU) is an arc fault detection device designed to
detect series arcs in DC photovoltaic installations. The ADU monitors the current
flow at the string level. The ADU detects a range of arc faults from 100 VDC 1 A to
1000 VDC 40 A. The ADU can detect arcing events over a maximum of 66 meters
upstream or downstream of the installed location.
When an arc fault occurs, the information is provided using the following methods:
• Fault LED lights
• Buzzer provides an audio alarm
• Message
Arc fault detected
is displayed on the inverter screen
• Inverter stops operation and disconnects from the grid
In addition, the ADU has an alarm output connector for activating external alarms/
actuators for follow-up of the arc fault detection.
ADU Overview
The connection box contains the optional ADU for inverters that provide AFCI
detection.
Grounding stud
AC input
DC inputs
DC disconnect
LEDs
ADU
Reset button
Figure 6‑1. Optional ADU features and connection box components
Advanced Energy® AE 3TL Inverters
Chapter
6
570-1003552-05A
Operating the Arc Fault Detection Unit
6‑1
Summary of Contents for AE 3TL 1000 Series
Page 2: ......
Page 12: ...Advanced Energy xii 570 1003552 05A List of Tables...
Page 14: ...Advanced Energy xiv 570 1003552 05A List of Figures...
Page 26: ...Advanced Energy 1 12 Safety and Product Compliance Guidelines 570 1003552 05A...
Page 64: ...Advanced Energy 4 28 Installing 570 1003552 05A...
Page 86: ...Advanced Energy 6 4 Operating the Arc Fault Detection Unit 570 1003552 05A...
Page 92: ...Advanced Energy 7 6 Data Monitoring and Controls 570 1003552 05A...
Page 110: ...Advanced Energy 9 14 Troubleshooting and Solar Energy Technical Support 570 1003552 05A...
Page 116: ...Advanced Energy A 6 Specifications 570 1003552 05A...
Page 120: ...Advanced Energy B 4 System and Mechanical Diagrams 570 1003552 05A...