6TANTP507-1E
TOTAL ACCESS
3000/3010
NTP-507
Page 1 of 6
Total Access
®
3000/3010 System Manual
© 2002, ADTRAN, Inc.
1.1
SCU Replacement in a Total Access 3000/3010 Shelf
NOTE
References to common, but differing, parameters between the Total
Access 3000 and the Total Access 3010, such as number of slots, will be
conveyed by the convention a/b. The “a” represents the Total Access 3000
parameter and the “b” represents the Total Access 3010 parameter. For
example, the differing number of access slots in the two platforms, 28 for
the Total Access 3000 and 22 for the Total Access 3010, would be
displayed “28/22.”
1.1.1
Introduction
This procedure provides step-by-step instructions for the replacement of a Total
Access System Controller Unit (SCU), into a Total Access central office shelf.
Replacement procedures include the removal of the product from its packaging and
inspecting for damage, seating the unit in the shelf, provisioning and turnup.
1.1.2
Prerequisite Procedures
NOTE
The following procedures must be completed prior to replacing the SCU
module. All passwords, addresses and other information such as CLLI code
and TIRKS ID must be written down prior to installing the replacement SCU.
1. Logon to the system
2. From the Total Access Menu, select option 1,
System Controlle
r, and press
<Enter>.
3. From the System Controller Menu, select option 2,
Provisioning
, and press
<Enter>.
4. From the Provisioning Menu, select option 1,
General
, and press <Enter>.
5. From the General Menu, write down the settings for the following parameters:
1.) Date
2.) Time
3.) Auto-Logoff
6. Once all the above information has been written down, select option 1,
Management Ports
, and press <Enter>.