61175044L2-22B

AC/DC POWER SUPPLY AND BATTERY CHARGER

JOBAid, 61175044L2-22B, December 2002

Technical Support 1-888-4ADTRAN (1-888-423-8726)

Copyright 

 2002 ADTRAN, All Rights Reserved

MOUNTING INSTRUCTIONS

Remove the Total Access 750/850 AC/DC Power Supply 
(ADTRAN P/N 1175043Lx) from the box and inspect for 
damage. If damage is apparent, contact your carrier or 
supplier.

Place the power supply with the power cord oriented 
downward.

Use four #6 x 3/8" machine screws (supplied) to mount the 
power supply to either side of the Total Access 750/850 shelf.

Note: Threaded mounting holes are provided on both sides of 

the shelf.

Note: For battery backup installations, it is recommended to 

mount the power supply on the left side of the Total 
Access 750/850 shelf, next to the battery cover hinge.

Note: Alternatively, the power supply can be mounted to the 

backboard with four #6 x 1" wood screws (not supplied).

The device complies with Part 15 of the FCC rules. Operation is 
subject to the following two conditions: (1) This device may not 
cause harmful interference, and (2) this device must accept any 
interference received, including interference that may cause 
undesired operation.

Changes or modifications not expressly approved by ADTRAN
could void the user's authority to operate this equipment.

WARRANTY

Warranty for Carrier Network products manufactured by 
ADTRAN and supplied under Buyer's order for use in the U.S. is 
ten (10) years. For a complete copy of ADTRAN's U.S. Carrier 
Networks Equipment Warranty: (877) 457-5007, Document 414.

STATUS LEDS

RELAYS

Alarm Relay

Provided for customer use

Battery Disconnect Relay

Disconnects battery pack from the system if the battery voltage falls below -40 VDC

Prevents damage to batteries

CIRCUIT BREAKER

 

3- amp circuit breaker

 Protects 

unit 

from 

over 

current

 

Rocker button extends out from front panel when tripped

 

Reset by pushing in on the rocker button

GROUNDING

An 18 AWG or larger ground wire is required to connect additional ground connector to "ground
bus" in customer equipment room.

ELECTRICAL SPECIFICATIONS

TELECOMMUNICATIONS CODES

AC Power Operation (AC power only)

Battery Operation (AC power supply or battery backup)

GREEN

OK

GREEN

OK (charging)

YELLOW

Power Fail

YELLOW

Discharging

RED

Power Fail

RED

Low (<-40 V)

OFF

Power Fail

OFF

Disconnected

Condition

Alarm Relay

Normal

Open

AC Power Failure/
Battery Backup engaged

Cycles open/closed once per second if AC voltage <88 Vrms at full load and battery 
backup is connected

Battery voltage <-45V

Stays closed if voltage <-45 VDC to indicate that battery is becoming depleted

AC/DC POWER

SUPPLY AND

BATTERY CHARGER

P/N:

1175043L1

CLEI: SIMPAAAARA
P/N:

1175043L2

CLEI: SIMPAADARA
P/N:

1175043L3

CLEI: SIMPAAEARA

C A U T I O N ! 

SUBJECT TO ELECTROSTATIC DAMAGE

OR DECREASE IN RELIABILITY.

HANDLING PRECAUTIONS REQUIRED.

Note:  The AC/DC Power Supply 

and Battery Charger is 
designed for use with the 
Total Access 750 and 850. 
It is not used with the Total 
Access 612/616/624 units.

AC input: 115 V nominal

Range: 90 to 132 VAC

DC output: -54 V, 60 W average, 100 W peak

Battery charging: 16 hr nominal, 24 hr maximum

Battery discharge: Up to 8 hours

1

2

3

Code

Input

Output

PC

F

C

TC

IC

E