26
4.1.7.3 Energy Type
4.1.7.4 Pre-Divider
4.1.7.5 High Time
• Select the corresponding energy parameters for pulse output. The selectable parameters
include Import kWh, Export kWh, Import kVARh, Export kVARh, and can also be OFF. The
default value is Import kWh.
• Steps of setup are as follows:
1. Press ENTER key on the menu page to enter energy type setting.
2. Use UP and DOWN key to select the corresponding energy parameter.
3. Press ENTER key to finish setting and return to the previous menu.
※ Press LEFT key to cancel input and return to the previous menu.
• Pre-Divider setting. The setting range is 1 ~ 9999,The default value is 1.
• Steps of setup are as follows:
1. Press ENTER key on the menu page to enter pre-divider setting.
2. Press UP or DOWN key to select the numeric.
3. Press LEFT key move to the next digit.
4. Repeat step 2 to 3 until finishing 4-digit setting of pre-divider, press ENTER key to
save and return to the previous menu.
※ Press LEFT key and hold 2 seconds to cancel input and return to the previous menu.
• Pulse output high level time setting, the setting range is 0 ~ 5000 mS, 0 means 50% duty
of the high and low level. The default value is 0.
• Steps of setup are as follows:
1. Press ENTER key on the menu page to enter high time setting.
2. Press UP or DOWN key to select the numeric.
3. Press LEFT key move to the next digit.
4. Repeat step 2 to 3 until finishing 4-digit setting of high time, press ENTER key to save
and return to the previous menu.
※ Press LEFT key and hold 2 seconds to cancel input and return to the previous menu.
4.1.8 Energy Unit
• Energy unit setting, the unit that can be selected are 0.0001kWh、0.001kWh、0.01kWh、
0.1kWh、1kWh、0.01MWh、0.1MWh. The default value is 0.1kWh.
• Steps of setup are as follows:
1. Press ENTER key on the menu page to enter energy unit setting.
2. Use UP or DOWN key to select energy unit.
3. Press ENTER key to finish setting and return to the previous menu.
※ Press LEFT key to cancel input and return to the previous menu.