background image

MVX 206  Two-Wire Non-Isolated  Millivolt Transmitter 
MVX 226  Two-Wire Isolated Millivolt Transmitter 

Instruction Manual 

1.0  INTRODUCTION 

These instructions refer to the above models. Supplementary 

sheets are attached if the unit has special options or features. 

For detailed specifications, see page 4 or refer to the Data 

Bulletin.  All AD TECH instruments are factory calibrated and 

supplied with a label detailing the calibration.  Adjustments 

are  normally  not necessary.  A  simple  check  should  be 

performed to verify calibration before installation to ensure 

that it matches the field requirement. 

2.0  GENERAL DESCRIPTION 

The  ADTECH  Model  MVX 206  and  MVX  226  Two-Wire 

Millivolt Transmitters provides high accuracy conversion of 

-20 to 100 mv input signals to a standard 4-20 ma de process

signal.

The  MVX 226  provides  600  volts  AC  or  1000  volts  de 

isolation from the input to output/power supply, whereas the 

MVX 206 is non-isolated. 

The primary features of the MVX 206 and MVX 226 are: 

• Wide range (-20) to 100 mv switch selectable.

• Zero Suppression of up to 100% of the major range

with a 16 position switch.

• Field  adjustable  via  internal  switches  and  front

potentiometers.

• High  accuracy,  repeatability,  and  ambient  effect

stability.

• RFI resistant.

• NO INTERACTION of ZERO and SPAN.

• Small size-DIN mounting package. Only 

"w x 3.1 "h

X 3.6" d.

• Options  for  NEMA  housings,  SNAP  TRACK  and

surface mounting (DIN 46 277 standard).

3.0  INSTALLATION 

The instrument is supplied in a non-metallic general purpose 

DIN  rail  mount  enclosure  as  standard.  NEMA  4  and  7 

enclosures are optionally available. Installation area/location 

must agree with the supplied instruments including operating 

temperature and ambient conditions. For detailed mounting 

and installation refer to page 4 inside. 

Electrical Connections 

The  wire  used  to  connect  the  instrument  to  the  control 

system 

Input/ Output 

should be twisted pair(s) and sized 

according to normal practice. Shielded cable is not normally 

necessary (if used, the shield must be grounded at the input 

of the ADTECH instrument and left floating at the sensor). 

six position compression terminal block is provided for the 

1/0 and power connections. A housing ground terminal is not 

required due to non-metallic housing. 

Controls 

Instrument controls consist of the following: 

• Two 16 position range  switches  for 

COARSE 

ZERO

and SPAN control.

• One4 position jumper for input of major range selection.

• One 2-position jumper for 20 mv elevation.

• Two multiturn potentiometers; 

FINE 

ZERO and SPAN

controls on front of the instrument.

4.0  MAINTENANCE 

These instruments are electronic and require no maintenance 

except periodic cleaning and calibration. 

If the unit appears to be mis-operating,  field wiring and/or 

associated circuits should be checked.  MOST problems are 

traced to these areas. 

If  the  problem  appears  to  be  the  instrument,  it  may  be 

checked  as  installed  or  removed  for  a  bench  check  as 

detailed in sections 6.0 and 7.0. 

5.0  CONNECTIONS 

Standard connections are shown below and on the instrument 

face  plate,  Data  Bulletin  or  on  attached  supplementary 

sheets. 

-1-

ADTECH 

MVX 

TWO WIRE 

TRANSMTR 

(9/96) 

190-A-000070-A