MVX 106  Two-Wire Non-Isolated Millivolt Transmitter 

MVX 126  Two-Wire Isolated Millivolt Transmitter 

Instruction Manual 

1.0  INTRODUCTION 

These instructions refer to the above models. Supplementary 

sheets are attached if the unit has special options or features. 

For detailed specifications,  see page 4 or  refer to the Data 

Bulletin.  All ADTECH instruments are factory calibrated and 

supplied with a label detailing the calibration. Adjustments are 

normally not necessary. A simple check should be performed 

to verify calibration before installation to ensure that it matches 

the field requirement. 

2.0  GENERAL DESCRIPTION 

The  ADTECH  Model  MVX 106  and  MVX  126  Two-Wire 

Millivolt Transmitter  provides  high  accuracy  conversion  of 

-20 to 100 mv input signals to a standard 4-20 ma de process

signal.

The MVX 126 provides 350 volts AC or 600 volts de isolation 

from the input to outpuVpower supply, whereas the MVX 106 

is non- isolated. 

The primary features of the 

MVX 

106 and MVX 126 are: 

• Wide range (-20) to 100 mv switch selectable.
• Zero Suppression of up to  100%  of the major range

with a 16 position switch.

• Field  adjustable  via  front  accessible switches  and

potentiometers.

• High  accuracy,  repeatability,  and  ambient  effect

stability.

• RFI Protection:  Standard.

• NO INTERACTION of ZERO and SPAN.

• Small  size  - universal  mounting  package  provides

integral RFI protection and an environmental seal.

• Options for NEMA housings, SNAP TRAK and DIN rail

mounting (DIN 46 277 standard).

3.0  INSTALLATION 

The  instrument  is  supplied  in  a  sturdy  die  cast  aluminum 

housing with an epoxy paint finish. The housing is gasketed 

providing an environmental  seal for the internal electronics 

and  controls. NEMA 4,  7 and  12,  Snap  Track  and  DIN  rail 

(TS32 and TS35) are optionally available. Installation area/ 

location must agree with the supplied instruments including 

operating temperature and ambient conditions. 

Mounting 

Refer  to page 3 for outline and mounting dimensions.  The 

standard instrument is surface mounted with integral #6-32 

S.S. thumb screws. 

Electrical Connections 

The wire used to connect the instrument to the control system 

Input/ Output 

should be twisted pair(s) and sized according 

to normal practice. Shielded cable is not normally necessary 

(if  used,  the  shield  must  be  grounded  at  the  input  of  the 

ADTECH instrument and left floating at the sensor). 

Two  barrier  terminal  blocks  with  #6-32  screws  and  0.325" 

spacing are provided for I /  0 connections. 

Controls 

Instrument controls consist of the following: 

• Two 16 position range  switches  for 

COARSE 

ZERO

and SPAN control.

• One 8 position dip switch for selection of major range.

• Two multiturn potentiometers; 

FINE 

ZERO and SPAN

controls.

All controls are accessible through the front of the instrument. 

An integral gasketed cover provides an environmental seal for 

the controls and internal electronics when the controls are not 

in use. 

4.0  MAINTENANCE 

These instruments are electronic and require no maintenance 

except periodic cleaning and calibration. 

If  the unit  appears  to  be  mis-operating,  field  wiring and/or 

associated circuits should be checked.  MOST problems are 

traced to these areas. 

If the problem appears to be the instrument, it may be checked 

as  installed  or  removed  for  a  bench  check  as  detailed  in 

sections 6.0 and 7.0. 

5.0  CONNECTIONS 

Standard connections are shown below and on the instrument 

face plate, Data Bulletin or on attached supplementary sheets. 

CD  © 

®  © 

,,� 

(+) 

YNPUr-1 

MV 

LOOPl+I 

HSUPPLY 

® 

®  I 

CAUTION:  Terminal  #3  should  not  have  any  customer 

connections. 

-1-