MVT 306L Non-Isolated Millivolt Transmitter 

MVT 326L Isolated Millivolt Transmitter 

Instruction Manual 

1.0  INTRODUCTION 

These instructions refer to the above model. Supplementary 

sheets are attached if the unit has special options or features. 

For detailed specifications, see page 4 or refer to the Data 

Bulletin.  All ADTE CH instruments are factory calibrated and 

supplied with a label detailing the calibration.  Adjustments 

are  normally  not necessary.  A  simple  check  should  be 

performed to verify  calibration before installation to ensure 

that it matches the field requirement. 

2.0  GENERAL DESCRIPTION 

The  ADTECH  MVT  306L  and  MVT  326L  are  low  power 

millivolt transmitters that accept 0.5 to 100 mv de input and 

provide two of the standard signal outputs namely 1-5 vdc or 

0-5 vdc.

This model consumes very low power,  typically 3.5 made 

and is specially designed for remote bettery on solar panel 

powered applications. 

The MVT 326L provides 600 vac or 1 000 vdc isolation of the 

input from the output and de power supply. The MVT 306L 

provides no isolation between input, output or de power. 

Both models are powered by de power 7-42 vdc in such a 

way that the output negative connection is common with the 

power supply. This is why it is called the three wire transmitter. 

3.0  INSTALLATION 

The instrument is supplied in a general purpose compact 

plastic enclosure as standard.  NEMA 4 and 7 enclosure are 

optionally available.  Installation area/location must agree 

with the supplied instruments including operating temperature 

and ambient conditions. 

Electrical Connections 

The  wire  used  to  connect  the  instrument  to  the  control 

system 1/0 should be a twisted pair(s) and sized according 

to normal practice. Shielded cable is not normally necessary 

(if used, the shield must be grounded at the input negative 

of the ADTECH instrument and left floating at the sensor). 

Six position compression terminals are provided for 1/0 and 

power connections. A housing ground terminal is not required 

due to non-metallic housing. 

Controls 

Multiturn  fine  ZERO  and  SPAN  controls  are  provided  to 

calibrate the instrument. The multiturn controls are accessible 

through the front panel and are clearly marked for ease of 

use. Internal range selection controls are listed in the section 

8.0 Tables and as follows. 

Two  16 position rotary switches for coarse zero and span 

control. 

Pin  Jumpers  for  major  range;  zero  elevation  and  output 

selection. 

4.0  MAINTENANCE 

These instruments are electronic and require no maintenance 

except periodic cleaning and calibration verification.  If the 

unit appears to be mis-operating it should be checked as 

installed per section 6.0 or removed for a bench check per 

sections 6.0-7.0.  MOST problems are traced to field wiring 

and/or associated circuits.  If the problem appears to be with 

the instrument, proceed to sections 6.0 and 7.0. 

5.0  CONNECTIONS 

Standard connections are shown below and on the instrument 

face  plate,  Data  Bulletin  or  on  attached  supplementary 

sheets. 

ADTECH 

COM. 

NOTE: MVT306L and 326L Connections are identical. 

-1-

190-A-000083

Summary of Contents for MVT 306L

Page 1: ...lable Installation area location must agree with thesuppliedinstrumentsincludingoperatingtemperature and ambient conditions Electrical Connections The wire used to connect the instrument to the control system 1 0 should be a twisted pair s and sized according to normal practice Shielded cableis not normallynecessary if used the shield must be grounded at the input negative of the ADTECH instrument...

Page 2: ... is located on the input pcb furthest from the fine potentiometer controls The COARSE SPAN switch SW2 is located to the right of the Coarse Zero Switch Note Steps D G E are applicable when the unit is opened for re ranging to different Zero or Span E Apply an input corresponding to the zero input Adjust the fine ZERO control fully counterclockwise Adjust the COARSE ZERO switch to a position where ...

Page 3: ...TABLE 2 Zero Elevation 0mV I J3 B 20mV I J3 A Note All input jumpers located on larger pcb 8 0 TABLES 8 1 PCB LAYOUT MVT 326L Isolated Millivolt 3 OUTPUT TABLE 2 Output Range 1 5 vdc I J6 A 0 5 vdc I J6 B Note J6 is on the larger pcb MVT 306L Non Isolated Millivolt 190 A 000083 ...

Page 4: ...31 to 85 C operating _ jo to 200 F 40 to 93 C storage k Power Supply Effect 0 005 over operating range I Isolation MVT 326 only lnpuVOutput 600 vac 1000 vdc Note All accuracies are given as a percentage of span POWER a 7 to 42 vdc 3 5 mA typical 5 mA maximum MECHANICAL a Electrical Classification general purpose b Connection Screw compression type accepts up to 14 AWG c Controls One 4 position jum...

Reviews: