5 Electrical connections
5.1 Requirements
ATTENTION
Damage to the electronics!
The electronics can be damaged if connectors are connected or disconnected while power is still
being applied.
•
Make sure that no power is being applied when connecting and disconnecting connectors.
ATTENTION
Damage due to electrostatic discharge!
Damage to the device can be caused by electrostatic discharge.
•
Always adhere to the safety measures applicable when handling components at risk of being
damaged by electrostatic discharge.
WARNING
Hazard due to electric shock with fatal consequences
With device variants with an
AC voltage supply
, the electrical connection must be
performed by a specialist electrical engineer.
Before commissioning, a
protective earth conductor test
must be carried out
according to VDE 0701/0702
to ensure that the protective earth is functioning
optimally.